8.7 PWM output function<br />

Function<br />

6F3B0253<br />

8. Special I/O Functions<br />

This function is used to output a variable duty cycle pulse train. The controllable duty<br />

cycle is 0 to 100 % (1 % units).<br />

PWM<br />

ON duty 50% 70% 60%<br />

T T T T = Pulse cycle<br />

The PWM output is enabled when the pulse enable flag is ON. While the pulse enable<br />

flag is ON, the duty cycle (ON duty) can be changed by changing the duty setting<br />

value (0 to 100).<br />

The frequency setting is available in the range of 50 to 5000 Hz (1 Hz units) before<br />

turning ON the pulse enable flag. The frequency changing is not allowed while the<br />

pulse enable is ON.<br />

Note that the minimum ON/OFF pulse duration is 100 µs. Therefore, the controllable<br />

ON duty range is limited depending on the frequency setting as follows. If the ON duty<br />

setting value is not available (within 0 to 100), the pulse width error flag comes ON.<br />

(PWM output operation is continued but the duty cycle is not guaranteed)<br />

Frequency Cycle time Available ON duty<br />

50 - 100 Hz 20 - 10 ms 0 to 100 %<br />

200 Hz 5 ms 0, 2 to 98, 100 %<br />

1000 Hz 1 ms 0, 10 to 90, 100 %<br />

5000 Hz 200 µs 0, 50, 100 %<br />

Related registers<br />

SW26: Function selection. Refer to section 8.1.<br />

Function Register/<br />

device<br />

Remarks<br />

PWM pulse Y020<br />

Pulse enable flag S270 Output is enabled when ON<br />

Frequency setting register SW28 Data range: 50 to 5000<br />

ON duty setting register SW29 Data range: 0 to 100<br />

Pulse width error flag S26D ON at error (reset OFF automatically)<br />

ON duty setting error flag S26E ON at error (reset OFF automatically)<br />

Frequency setting error flag S26F ON at error (reset OFF automatically)<br />

Note) If the setting value of SW28 or SW29 is out of the allowable range, the<br />

frequency setting error flag (S26F) or the ON duty setting error flag (S26E)<br />

comes ON. (PWM output operation is continued with previous ON duty setting)<br />

Basic Hardware and Function 273<br />