7. Instructions<br />

FUN 070 SHR n bit shift right<br />

Expression<br />

Input −[ A SHR n → B ]− Output<br />

166 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, the data of register A is shifted n bits to the right (LSB direction) including<br />

the carry flag (CF = S050), and stored in B. 0 is stored in upper n bits. After the operation, if the<br />

right most bit (LSB) is ON, the output is turned ON.<br />

Execution condition<br />

Input Operation Output CF<br />

OFF No execution OFF −<br />

ON Execution When LSB = 1 ON Set or reset<br />

When LSB = 0 OFF Set or reset<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

n Shift bits 1 - 16<br />

B Destination √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When X007 is changed from OFF to ON, the data of RW18 is shifted 5 bits to the right and the<br />

result is stored in RW20.<br />

The figure below shows an operation example.<br />

(MSB) (LSB)<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

RW18 0 1 0 0 0 0 1 0 1 0 0 1 1 0 1 0<br />

CF<br />

RW20 0 0 0 0 0 0 1 0 0 0 0 1 0 1 0 0 1<br />

(Result)<br />

0 R001 is turned OFF<br />