4.6 I/O wiring<br />

! CAUTION<br />

6F3B0253<br />

4. Installation and Wiring<br />

• Refer to sections 2.4 and 3 for instructions on how to properly wire the I/O<br />

terminals.<br />

• 0.75mm 2 (18 AWG) to 0.3mm 2 (22 AWG) wires are recommended for I/O signals.<br />

• Separate the I/O signal cables from high-power cables by at least 200mm.<br />

• If expansion rack or unit is used, separate the expansion cable from the power and<br />

I/O signal cables by or unit at least 50mm.<br />

• It is recommended to separate the input signal cables from output signal cables.<br />

Input<br />

signal<br />

1. Turn off power before wiring to minimize the risk of electrical shock.<br />

2. Exposed conductive parts of wire can cause electrical shock. Use<br />

crimp-style terminals with insulating sheath or insulating tape to cover<br />

the conductive parts. Also close the terminal covers securely on the<br />

terminal blocks when wiring has been completed.<br />

3. Turn off power before removing or replacing units, modules, terminal<br />

blocks or wires. Failure to do so can cause electrical shock or damage<br />

to the <strong>T1</strong>-<strong>16S</strong> and related equipment.<br />

<strong>T1</strong>-<strong>16S</strong> 200mm<br />

or more<br />

Output<br />

signal<br />

High-power<br />

cable<br />

Basic Hardware and Function 61<br />