7. Instructions<br />

< Note ><br />

254 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

(1) The XFER instruction is not executed as error in the following cases. In these cases, the instruction error<br />

flag (ERF = S051) is set to ON. If the ERF is set to ON once, it remains ON until resetting to OFF by<br />

user program.<br />

• The RS-485 port designation is other than H0030 and 0.<br />

• The Inverter number designation is other than 0 to 63.<br />

• Operation mode setting for RS-485 port is other than the Inverter connection mode.<br />

(2) This XFER instruction must be programmed in the Main program.<br />

(3) During the instruction input is ON, the data contents in the data table specified by A can be changed.<br />

However, parameters specified by B cannot be changed.<br />

(4) In the Data exchange mode (mode 0) and the Monitor mode (mode 1), the <strong>T1</strong>-<strong>16S</strong> scans from #0 to the<br />

specified number. Therefore the Inverter number should be consecutive starting with 0.<br />

If an Inverter is disconnected from the network, the <strong>T1</strong>-<strong>16S</strong> checks its existence periodically. When you<br />

turn off power to an Inverter for maintenance purpose and turn on again, it is recommended to reset the<br />

instruction input to re-configure the network.<br />