9. Maintenance and Checks<br />

9.3 Periodic checks<br />

! CAUTION<br />

Check the <strong>T1</strong>-<strong>16S</strong> based on the following items every six months. Also perform<br />

checks when the operating environment is changed.<br />

278 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

1. Pay special attention during the maintenance work to minimize the risk<br />

of electrical shock.<br />

2. Turn off power immediately if the <strong>T1</strong>-<strong>16S</strong> or related equipment is<br />

emitting smoke or odor. Operation under such situation can cause fire<br />

or electrical shock.<br />

Item Check Criteria<br />

Power supply Measure the power voltage at the <strong>T1</strong>- 85 - 132/170 - 264Vac (AC PS)<br />

<strong>16S</strong>’s power terminals.<br />

20.4 - 28.8Vdc (DC PS)<br />

Check that the terminal screw is not<br />

loose.<br />

Not loose<br />

Check that the power cable is not<br />

damaged.<br />

Not damaged<br />

Installation Check that the unit is installed Not loose, no play<br />

condition securely.<br />

Check that the I/O module is inserted<br />

securely. (if any)<br />

Not loose, no play<br />

Check that the expansion rack/unit is<br />

installed securely. (if any)<br />

Not loose, no play<br />

Check that the expansion cable is<br />

connected securely and the cable is<br />

not damaged. (if any)<br />

Not loose, not damaged<br />

Check that the I/O module on the<br />

expansion rack is inserted securely. (if<br />

any)<br />

Not loose, no play<br />

Input/output Measure the input/output voltage at The voltage must be within the<br />

the <strong>T1</strong>-<strong>16S</strong>’s terminals.<br />

specified range.<br />

Check the input status LEDs. The LED must light normally.<br />

Check the output status LEDs. The LED must light normally.<br />

Check that the terminal block is<br />

installed securely.<br />

Not loose, no play<br />

Check that the terminal screw is not Not loose, not contacting the<br />

loose and the terminal has a sufficient<br />

distance to the next terminal.<br />

next terminal<br />

Check that the each I/O wire is not<br />

damaged.<br />

Not damaged<br />