6F3B0253<br />

7. Instructions<br />

• <strong>Manual</strong> mode<br />

In this mode, the manipulation value MV can be directly controlled by the input value of MMV.<br />

MV differential limit for manual mode DMMV is effective. MH/ML and DMV are not effective.<br />

When mode is changed from manual to auto or cascade, the operation is started from the current MV.<br />

• Cascade mode<br />

This is a mode for PID cascade connection. PID is executed with CSV as set value.<br />

Different from the auto mode, set value differential limit is not effective. Manipulation value upper/lower<br />

limit MH/ML and differential limit DMV are effective.<br />

Bump-less changing from cascade mode to manual mode is available. (<strong>Manual</strong> mode manipulation<br />

value MMV is over-written by current MV automatically. MMV ← MV)<br />

And, bump-less changing from cascade mode to auto mode is available. (Auto mode set value ASV is<br />

over-written by current CSV automatically. ASV ← CSV)<br />

• MV tracking<br />

This function is available in auto and cascade modes. When the tracking designation ( A+5 bit 2) is ON,<br />

tracking input TMV is directly output as MV.<br />

Manipulation value upper/lower limit MH/ML is effective, but differential limit DMV is not effective.<br />

When the tracking designation is changed to OFF, the operation is started from the current MV.<br />

Note<br />

• PID3 instruction is only usable on the main-program.<br />

• PID3 instruction must be used under the constant scan mode. The constant scan interval can be selected<br />

in the range of 10 to 200 ms, 10 ms increments.<br />

• The data handled by the PID3 instruction are % units. Therefore, process input value PVC, manipulation<br />

value MV, etc., should be converted to % units (scaling), before and/or after the PID3 instruction. For this<br />

purpose, the function generator instruction (FUN165 FG) is convenient.<br />

Basic Hardware and Function 223<br />