FUN 050 OR OR<br />

Expression<br />

Input −[ A OR B → C ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, this instruction finds logical OR of A and B, and stores the result in C.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

B source √ √ √ √ √ √ √ √ √ √ √ √<br />

C OR √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When R012 is ON, logical OR operation is executed for the data of RW13 and RW20, and the<br />

result is stored in D0031.<br />

If the data of RW13 is H5678 and RW20 is H4321, the result H5779 is stored in D0031.<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

RW13 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0<br />

5 6 7 8<br />

OR<br />

RW20 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1<br />

4 3 2 1<br />

D0031 0 1 0 1 0 1 1 1 0 1 1 1 1 0 0 1<br />

5 7 7 9<br />