FUN 097 >= Greater than or equal<br />

Expression<br />

Input −[ A >= B ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, the data of A and the data of B are compared, and if A is greater than or<br />

equal to B, the output is turned ON.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution A ≥ B ON<br />

A < B OFF<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Compared<br />

√ √ √ √ √ √ √ √ √ √ √ √<br />

data<br />

B Reference<br />

data<br />

Example<br />

√ √ √ √ √ √ √ √ √ √ √ √<br />

When R00C is ON, the data of D0125 is compared with the data of D0020, and if the data of<br />

D0125 is greater than or equal to the data of D0020, R020 is turned ON.<br />

If the data of D0125 is 3000 and that of D0020 is 3000, the comparison result is true.<br />

Consequently, R020 is turned ON.<br />

D0125 3000 ≥ D0020 3000 R020 is ON<br />

If the data of D0125 is -1500 and that of D0020 is 0, the comparison result is false.<br />

Consequently, R020 is turned OFF.<br />

D0125 -1500 < D0020 0 R020 is OFF<br />

Note<br />

• This instruction deals with the data as signed integer (-32768 to 32767).<br />

Basic Hardware and Function 179<br />