Broadcast mode (Mode 4) ><br />

6F3B0253<br />

7. Instructions<br />

When the instruction input comes ON with the operand B+1 is 4, the Broadcast mode (mode 4)<br />

is selected. In this mode, the <strong>T1</strong>-<strong>16S</strong> sends the user specified Write command to all the<br />

Inverters as broadcast.<br />

This mode is useful to send Run/Stop command to all the Inverter at the same time.<br />

Repeat<br />

Sends the specified command with command data to all Inverters (broadcast)<br />

Checks the acknowledge from #0 Inverter<br />

The Inverter number specified by the operand B is ignored.<br />

The scan execution status and the Inverter communication status are stored in the operand<br />

B+2 to B+7. (only #0 Inverter responds)<br />

The command code and the command data setting registers are indirectly specified by the<br />

operand A and A+1.<br />

When the instruction input is reset to OFF, the operation is stopped after receiving the<br />

response from the Inverter.<br />

Example<br />

Data table designation Parameter & status RS-485 port<br />

D1000 4 RW200 (any 0 to 63) D1010 H0030 (fixed)<br />

D1001 3020 RW201 4 (mode 4) D1011 0 (fixed)<br />

RW202 Execution status<br />

RW203 Comm error code<br />

RW204<br />

RW205 Inverter comms<br />

RW206 status map<br />

RW207<br />

When the data for each operand are set as above, the following operation condition is specified.<br />

• D1000=4 & D1001=3020 ⇒ D3020 is specified as the command code setting register and D3021 is<br />

specified as the command data setting register.<br />

Data table:<br />

Register Data contents Signal direction<br />

D3020 Command code<br />

D3021 Command data → Write<br />

Example operation:<br />

For example, to send the Run forward command to all the Inverters, set the command code HFA00<br />

into D3020 and the value HC400 into D3021.<br />

For the command code and the command data format, refer to your Inverter manual.<br />

Basic Hardware and Function 253<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net