6F3B0253<br />

7. Instructions<br />

9 devices starting with R200 (R200 to R208) is specified as a shift register.<br />

When R010 is OFF, the data of the shift register is reset to 0. (R200 to R208 are reset to OFF)<br />

The carry flag (CF = S050) is also reset to OFF.<br />

While R010 is ON the following operation is enabled.<br />

• When X00A is ON (shift left), the data of the shift register is shifted 1 bit to the upper<br />

address direction when X009 is changed from OFF to ON. At the same time, the state of<br />

X008 is stored in the leading bit (R200). The output (R012) indicates the state of the highest<br />

bit (R208).<br />

• When X00A is OFF (shift right), the data of the shift register is shifted 1 bit to the lower<br />

address direction when X009 is changed from OFF to ON. At the same time, the state of<br />

X008 is stored in the highest bit (R208). The output (R012) indicates the state of the lowest<br />

bit (R200).<br />

The figure below shows an operation example.<br />

(When X00A is ON and X009 is changed from OFF to ON)<br />

CF R208 R207 R206 R205 R204 R203 R202 R201 R200 X008<br />

1 0 0 1 1 0 0 1 1 0<br />

1 0 0 1 1 0 0 1 1 0<br />

R012 is turned OFF<br />

(When X00A is OFF and X009 is changed from OFF to ON)<br />

X008 R208 R207 R206 R205 R204 R203 R202 R201 R200 CF<br />

1 0 0 1 1 0 0 1 1 0<br />

Shift result<br />

Shift result<br />

1 0 0 1 1 0 0 1 1 0<br />

R012 is turned ON<br />

Note<br />

• When the shift input is ON, the shift operation is performed every scan. Use a transitional<br />

contact for the shift input to detect the state changing.<br />

• For the data input, the shift input and the enable input, direct linking to a connecting point is not<br />

allowed. In this case, insert a dummy contact (always ON special device = S04F, etc.) just<br />

before the input. Refer to Note of Shift register FUN 074.<br />