10. Troubleshooting<br />

10.1.2 CPU check<br />

If the PWR (power) LED is lit but the RUN LED is not lit, check the following points.<br />

Check the position of the If it is not in R (RUN) position, turn the<br />

mode control switch switch to R (RUN) position.<br />

284 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Check the FLT (fault) LED If the FLT LED is lit or blinking, the <strong>T1</strong>-<strong>16S</strong><br />

is in the ERROR mode. Confirm the error<br />

message by connecting the<br />

programming tool. Refer to section 10.2.<br />

Is the RUN LED blinking ? If it is blinking, the <strong>T1</strong>-<strong>16S</strong> is in the HOLD<br />

mode. Check your program<br />

whether the HOLD device (S401) is<br />

not used.<br />

Connect the programming If the <strong>T1</strong>-<strong>16S</strong> stays in HALT mode even<br />

tool, and check the <strong>T1</strong>-<strong>16S</strong>’s when the mode control switch is changed,<br />

status the switch may be faulty.<br />

If the communication between the <strong>T1</strong>-<strong>16S</strong><br />

and the programming tool is not possible,<br />

the <strong>T1</strong>-<strong>16S</strong> may be faulty.<br />

10.1.3 Program check<br />

Check the user program based on the following points if it is running but the operation<br />

does not work as intended.<br />

(1) Whether duplicated coils are not programmed.<br />

(2) Whether a coil device and a destination of a function instruction are not<br />

overlapping.<br />

(3) Whether the ON/OFF duration of an external input signal is not shorter than the<br />

<strong>T1</strong>-<strong>16S</strong>’s scan time.<br />

(4) Whether a register/device, which is used in the main program, is not operated<br />

erroneously in the interrupt program.<br />

NOTE<br />

When you write/modify the program, it is necessary to execute the<br />

EEPROM write operation before turning off power to the <strong>T1</strong>. Otherwise the<br />

old program stored in the built-in EEPROM will be over-written, and your<br />

program modification will disappear.<br />