7. Instructions<br />

< Write command mode (Mode 3) ><br />

252 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

When the instruction input comes ON with the operand B+1 is 3, the Write command mode<br />

(mode 3) is selected. In this mode, the <strong>T1</strong>-<strong>16S</strong> sends the user specified Write command to the<br />

Inverter specified by the operand B, and repeats.<br />

Repeat<br />

Sends the specified command with command data to #n Inverter<br />

Checks the acknowledge<br />

The target Inverter number #n is specified by the operand B.<br />

The scan execution status and the Inverter communication status are stored in the operand<br />

B+2 to B+7.<br />

The command code and the command data setting registers are indirectly specified by the<br />

operand A and A+1.<br />

When the instruction input is reset to OFF, the operation is stopped after receiving the<br />

response from the Inverter.<br />

Example<br />

Data table designation Parameter & status RS-485 port<br />

D1000 4 RW200 5 D1010 H0030 (fixed)<br />

D1001 3010 RW201 3 (mode 3) D1011 0 (fixed)<br />

RW202 Execution status<br />

RW203 Comm error code<br />

RW204<br />

RW205 Inverter comms<br />

RW206 status map<br />

RW207<br />

When the data for each operand are set as above, the following operation condition is specified.<br />

• RW200=5 ⇒ The target Inverter number is 5. Therefore <strong>T1</strong>-<strong>16S</strong> communicates with #5 Inverter.<br />

• D1000=4 & D1001=3010 ⇒ D3010 is specified as the command code setting register and D3011 is<br />

specified as the command data setting register.<br />

Data table:<br />

Register Data contents Signal direction<br />

D3010 Command code<br />

D3011 Command data → Write<br />

Example operation:<br />

For example, to write the acceleration time parameter (10 seconds) to the #5 Inverter, set the<br />

command code H0009 into D3010 and the value 100 into D3011.<br />

For the command code and the command data format, refer to your Inverter manual.<br />