8. Special I/O Functions<br />

8.1 Special I/O function overview<br />

The <strong>T1</strong>-<strong>16S</strong> supports the special I/O functions as listed below.<br />

256 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function name Function summary Remarks<br />

Variable input filter<br />

constant<br />

High<br />

speed<br />

counter<br />

Single phase<br />

up-counter<br />

Single phase<br />

speedcounter<br />

Quadrature<br />

bi-pulse<br />

counter<br />

Input filter constant (ON/OFF delay time) can be set<br />

by user program. The setting range is 0 to 15ms<br />

(1ms units). Default value is 10ms. This function is<br />

applied for X000 to X007 (8 points as a block).<br />

Counts the number of pulses of single phase pulse<br />

train. 2 channels of pulse input are available. The<br />

countable pulse rate is up to 5KHz for each channel.<br />

Channel 1 … X000 count input, X002 reset input<br />

Channel 2 … X001 count input, X003 reset input<br />

Counts the number of pulses in a specified sampling<br />

time. The sampling time setting is 10 to 1000ms<br />

(10ms units). 2 channels of pulse input are available.<br />

The countable pulse rate is up to 5KHz for each<br />

channel.<br />

Channel 1 … X000 count input<br />

Channel 2 … X001 count input<br />

Counts the 2-phase pulses whose phases are shifted<br />

90° each other. Counts up when phase A precedes,<br />

and counts down when phase B precedes.<br />

The countable pulse rate is up to 5KHz.<br />

Phase A … X000<br />

Phase B … X001<br />

Reset …… X002<br />

Interrupt input function Immediately activates the corresponding I/O interrupt<br />

program when the interrupt input is changed from<br />

OFF to ON (or ON to OFF). 2 points of interrupt input<br />

are available.<br />

X002 … Interrupt 1 (I/O interrupt program #3)<br />

Analog setting<br />

function<br />

X003 … Interrupt 2 (I/O interrupt program #4)<br />

The value of the analog setting adjuster is converted<br />

into digital value (0 to 1000) and stored in the SW<br />

register. 2 adjusters are provided on the <strong>T1</strong>-<strong>16S</strong>.<br />

V0 … SW30<br />

V1 … SW31<br />

Pulse output function Variable frequency pulse train can be output. The<br />

available pulse rate is 50 to 5000Hz (1Hz units).<br />

Y020 … CW or Pulse (PLS)<br />

Y021 … CCW or Direction (DIR)<br />

PWM output function Variable duty cycle pulse train can be output. The<br />

available ON duty setting is 0 to 100% (1% units).<br />

Y020 … PWM output<br />

SW16 setting<br />

is necessary to<br />

use this<br />

function. (Note)<br />

Only one<br />

among these 4<br />

functions can<br />

be selected.<br />

SW16 is used<br />

to select the<br />

function.<br />

(Note)<br />

No function<br />

selection is<br />

required.<br />

Either one<br />

between these<br />

2 functions<br />

can be used.<br />

SW26 is used<br />

to select the<br />

function.(Note)<br />