7. Instructions<br />

Operation mode designation (B+1):<br />

246 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

B+1 Operation mode Description<br />

0 Data exchange mode Cyclically scans the connected Inverters (Control & Monitor)<br />

(Mode 0)<br />

(Inverter command: P+FA01&FA00 and R+FD00&FE07)<br />

1 Monitor mode<br />

Cyclically scans the connected Inverters (Monitor only)<br />

(Mode 1)<br />

(Inverter command: R+FD00&FE07)<br />

2 Read command mode Sends a read command to a specified Inverter<br />

(Mode 2)<br />

(Inverter command: R+ User designation)<br />

3 Write command mode Sends a write command to a specified Inverter<br />

(Mode 3)<br />

(Inverter command: P+ User designation)<br />

4 Broadcast mode Sends a write command to all the connected Inverters as broadcast<br />

(Mode 4)<br />

(Inverter command: P+ User designation)<br />

Inverter number (B):<br />

For the operation mode 0 and 1:<br />

It specifies the maximum Inverter number. For example, if it is 5, the <strong>T1</strong>-<strong>16S</strong> scans from #0<br />

through #5 Inverters and repeats. Setting range is 0 to 63.<br />

For the operation mode 2 and 3:<br />

It specifies the target Inverter number for sending commands. Setting range is 0 to 63.<br />

For the operation mode 4:<br />

This setting is ignored. The broadcast address (HFF) is used as Inverter number.<br />

Execution status (B+2):<br />

B+2<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

Communication error code (B+3):<br />

The communication error code responded from the Inverter is shown here. If 2 or more Inverters are error,<br />

the smallest Inverter number's error is stored. Refer to Inverter's manual for the error code.<br />

B+3 Meaning<br />

0 No error (Normal)<br />

Response time-out (No answer)<br />

Others Inverter error response (Refer to Inverter's manual)<br />

Inverter communication status map (B+4 to B+7):<br />

Shows the scan count.<br />

(0 → 1 → 2 → ... → 32767 → 0 → 1 ... )<br />

Comes 1 when the RS-485 port is busy. (No execution)<br />

This 4-word table shows the communication status map of each Inverter. (1: Normal / 0: Error or No<br />

answer)<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

B+4 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0<br />

B+5 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16<br />

B+6 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32<br />

B+7 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48<br />