7. Instructions<br />

FUN 078 RTR1 1 bit rotate right<br />

Expression<br />

Input −[ RTR1 A ]− Output<br />

172 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, the data of register A is rotated 1 bit to the right (LSB direction). The pushed<br />

out bit state is stored in the left most bit (MSB) and in the carry flag (CF = S050). After the<br />

operation, if the right most bit (LSB) is ON, the output is turned ON.<br />

Execution condition<br />

Input Operation Output CF<br />

OFF No execution OFF −<br />

ON Execution When LSB = 1 ON Set or reset<br />

When LSB = 0 OFF Set or reset<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Operation data √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When X007 is changed from OFF to ON, the data of RW15 is rotated 1 bit to the right.<br />

The figure below shows an operation example.<br />

(MSB) (LSB)<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

RW15 0 1 0 0 0 0 1 0 1 0 0 0 1 0 1 0<br />

CF<br />

RW15 0 0 1 0 0 0 0 1 0 1 0 0 0 1 0 1 0<br />

(Result)<br />

R001 is turned ON<br />