MCS<br />

MCR<br />

Expression<br />

Input [ MCS ]<br />

Master control set / reset<br />

[ MCR ]<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the MCS input is ON, ordinary operation is performed. When the MCS input is OFF, the state<br />

of left power rail between MCS and MCR is turned OFF.<br />

Execution condition<br />

MCS<br />

input<br />

Operation Output<br />

OFF Sets OFF the left power rail until MCR −<br />

ON Ordinary operation −<br />

Operand<br />

No operand is required.<br />

Example<br />

When X000 is OFF, Y021 and Y022 are turned OFF regardless of the states of X001 and<br />

X002.<br />

Equivalent circuit<br />

X000<br />

X001 Y021<br />

X002 Y022<br />

Note<br />

• MCS and MCR must be used as a pair.<br />

• Nesting is not allowed.<br />

Basic Hardware and Function 133<br />