3. I/O Application Precautions<br />

3.1 Application precautions for input signals<br />

! WARNING<br />

48 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

(1) Minimum ON/OFF time of the input signal<br />

The following conditions guarantee correct reading of the ON/OFF state of the input<br />

signal:<br />

Input ON time: ON delay time + the time for one scan<br />

Input OFF time: OFF delay time + the time for one scan<br />

The ON and OFF times of the input signals must be longer than these intervals.<br />

(2) Increasing the contact current<br />

The reliability of some contacts cannot be guaranteed by the specified input current. In<br />

this case, install an external bleeder resistor to increase the contact current.<br />

V<br />

I<br />

Configure emergency stop and safety interlocking circuits outside the<br />

<strong>T1</strong>-<strong>16S</strong>. Otherwise, malfunction of the <strong>T1</strong>-<strong>16S</strong> can cause injury or serious<br />

accidents.<br />

R<br />

I 2<br />

Bleeder resistor<br />

I 1<br />

<strong>T1</strong><br />

input<br />

circuit<br />

V<br />

R<br />

I I<br />

Wattage V<br />

=<br />

− 1<br />

2<br />

> × 3<br />

R<br />

(3) Connecting transistor output device<br />

An example of connecting a transistor output device to <strong>T1</strong>-<strong>16S</strong>’s input circuit is shown<br />

below.<br />

• For NPN open collector • For PNP open collector<br />

C<br />

<strong>T1</strong><br />

input<br />

circuit<br />

C<br />

<strong>T1</strong><br />

input<br />

circuit<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net