FUN 141 DI Disable interrupt<br />

Expression<br />

Input −[ DI ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, this instruction disables the execution of user designated interrupt operation,<br />

i.e. timer interrupt program and I/O interrupt programs.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

Operand<br />

No operand is required.<br />

Example<br />

In the above example, the interrupt is disabled when R000 is ON, and it is enabled when R000<br />

is OFF.<br />

Note<br />

• Refer to the EI instruction (FUN 140).<br />

• If an interrupt factor is occurred during the interrupt disabled state, the interrupt is kept waiting<br />

and it will be executed just after the EI instruction is executed.<br />

• The DI instruction can be used only in the main program.<br />

Basic Hardware and Function 209<br />