FUN 081 RTL n bit rotate left<br />

Expression<br />

Input −[ A RTL n → B ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, the data of register A is rotated n bits to the left (MSB direction), and stored<br />

in B. After the operation, if the left most bit (MSB) is ON, the output is turned ON.<br />

Execution condition<br />

Input Operation Output CF<br />

OFF No execution OFF −<br />

ON Execution When MSB = 1 ON Set or reset<br />

When MSB = 0 OFF Set or reset<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

n Shift bits 1 - 16<br />

B Destination √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When X008 is changed from OFF to ON, the data of RW18 is rotated 3 bits to the left and the<br />

result is stored in RW20.<br />

The figure below shows an operation example.<br />

∗<br />

(MSB) (LSB)<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

1 0 1 0 0 1 1 1 0 0 1 1 1 0 1 0<br />

CF<br />

1 0 0 1 1 1 0 0 1 1 1 0 1 0 1 0 1<br />

R002 is turned OFF<br />

RW18<br />

RW20 (Result)<br />

∗<br />

Basic Hardware and Function 175<br />