FUN 025 TMOV Table transfer<br />

Expression<br />

Input −[ A TMOV (n) B ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, the data of n registers starting with A are transferred to n registers starting<br />

with B in a block. The allowable range of the table size n is 1 to 1024 words.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Start of source √ √ √ √ √ √ √<br />

n Table size 1 - 1024<br />

B Start of<br />

destination<br />

√ √ √ √ √ √<br />

Example<br />

When R010 is ON, the data of D0500 to D0509 (10 registers) are block transferred to D1000 to<br />

D1009, and the output is turned ON.<br />

D0500 1111 D1000 1111<br />

D0501 2222 D1001 2222<br />

D0502 3333 Block transfer D1002 3333 10 registers<br />

D0509 12345 D1009 12345<br />

Note<br />

• The source and destination tables can be overlapped.<br />

Basic Hardware and Function 141<br />