03.01.2013 Views

Toshiba PROSEC T1-16S PLC User's Manual - CTi Automation

Toshiba PROSEC T1-16S PLC User's Manual - CTi Automation

Toshiba PROSEC T1-16S PLC User's Manual - CTi Automation

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

4.5 Power supply wiring<br />

! CAUTION<br />

Wire the power source to the <strong>T1</strong>-<strong>16S</strong> power supply terminals.<br />

Power source<br />

• Power conditions:<br />

Line filter<br />

6F3B0253<br />

4. Installation and Wiring<br />

1. Turn off power before wiring to minimize the risk of electrical shock.<br />

2. Applying excess power voltage to the <strong>T1</strong>-<strong>16S</strong> can cause explosion or<br />

fire. Apply power of the specified ratings described below.<br />

Insulation<br />

transformer<br />

<strong>T1</strong>-<strong>16S</strong><br />

AC power supply type DC power supply type<br />

Rated voltage 100 to 240Vac, +10/-15% 24Vdc, +20/-15%<br />

Frequency 50/60Hz, ±5% -<br />

Power consumption 45VA or less 18W or less<br />

Retentive power<br />

interruption<br />

Continuous operation for less than 10ms<br />

• 1.25mm 2 (16 AWG) twisted-pair cable should be used for the power cable.<br />

• The power cable should be separated from other cables.<br />

Basic Hardware and Function 59<br />