1.6 Programmer port function<br />

6F3B0253<br />

1. System Configuration<br />

The interface of the <strong>T1</strong>-<strong>16S</strong>’s programmer port is RS-232C. Normally this port is<br />

used to connect the programmer. However, this port can also be used for the<br />

computer link function.<br />

The computer link is a data communication function between computer or operator<br />

interface unit and the <strong>T1</strong>-<strong>16S</strong>. The data in the <strong>T1</strong>-<strong>16S</strong> can be read and written by<br />

creating simple communication program on the computer. The computer link protocol<br />

of the <strong>T1</strong>-<strong>16S</strong> is published in “<strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong> − Communication Function −”.<br />

Item Specifications<br />

Interface Conforms to RS-232C<br />

Transmission system Half-duplex<br />

Synchronization Start-stop system (asynchronous)<br />

Transmission speed 9600 bps (fixed)<br />

Transmission distance 15 m max.<br />

Framing Start bit:<br />

Data bits:<br />

Parity:<br />

Stop bit:<br />

1 bit<br />

8 bits (fixed)<br />

Odd or none<br />

1 bit (fixed)<br />

Protocol T-series computer link (ASCII)<br />

Programmer (binary)<br />

Transmission delay option 0 to 300 ms<br />

By using the multi-drop adapter (CU111), multiple <strong>T1</strong>-<strong>16S</strong>s can be connected on an<br />

RS-485 line. The T-series <strong>PLC</strong> programming software (T-PDS) can also be used in<br />

this configuration.<br />

Operator Interface<br />

<strong>T1</strong>-<strong>16S</strong><br />

C<br />

U<br />

Master Computer<br />

RS-232C RS-485 (1 km max.)<br />

<strong>T1</strong>-<strong>16S</strong><br />

C<br />

U<br />

<strong>T1</strong>-<strong>16S</strong><br />

C<br />

U<br />

Max. 32 <strong>T1</strong>-<strong>16S</strong>s<br />

<strong>T1</strong>-<strong>16S</strong><br />

Basic Hardware and Function 27<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net