10. Troubleshooting<br />

292 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Error message and related information Special Meaning and countermeasures<br />

Event Info 1 Info 2 Info 3 device<br />

Sys RAM check err Error Error data Test data S004 In the power-up initialization, an error has<br />

address<br />

S011 detected by system RAM read/write<br />

checking. (Error down and programming<br />

tool cannot be connected)<br />

Replace the unit if the error remains after<br />

power OFF and ON again.<br />

Sys ROM BCC error Illegal<br />

S004 BCC error has been detected in the system<br />

BCC<br />

S010 program in the ROM. (Error down and<br />

programming tool cannot be connected)<br />

Replace the unit if the error remains after<br />

power OFF and ON again.<br />

System power off Power OFF (no error)<br />

System power on Power ON (no error)<br />

Sub-r nesting err Program Address Sub-r No. The nesting of subroutines exceeds 3<br />

type - in the<br />

levels.<br />

block No. block<br />

(Error down)<br />

Correct the program.<br />

WD timer error Address 1 Address 2 S004 The watchdog timer error has occurred.<br />

S01F (Error down)<br />

If the error occurs frequently, replace the<br />

unit.<br />