FUN 147 F/F Flip-flop<br />

Expression<br />

Set input − S F/F Q − Output<br />

Reset input − R A<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the set input is ON, the device A is set to ON. When the reset input is ON, the device A is<br />

reset to OFF. When both the set and reset inputs are OFF, the device A remains the state. If both<br />

the set and reset inputs are ON, the device A is reset to OFF.<br />

The state of the output is the same as the device A.<br />

Execution condition<br />

Set Reset<br />

Operation Output<br />

input input<br />

OFF OFF No execution (A remains previous state) Same<br />

ON Resets A to OFF as A<br />

ON OFF Sets A to ON<br />

ON Resets A to OFF<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Device √ √ √<br />

Example<br />

When X003 is ON, R10E is set to ON. When X004 is ON, R10E is reset to OFF. If both are<br />

ON, R10E is reset to OFF.<br />

An example timing diagram is shown below.<br />

X003<br />

X004<br />

R10E<br />

Note<br />

• For the set input, direct linking to a connecting point is not allowed. In this case, insert a dummy<br />

contact (always ON = S04F, etc.) just before the input. Refer to Note of Shift register FUN 074.<br />

Basic Hardware and Function 215<br />