FUN 091 DPX Demultiplexer<br />

Expression<br />

Input −[ A DPX (n) B → C ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, the data of A is transferred to the register which is designated by B in the<br />

table, size n starting with C.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Normal execution OFF<br />

Pointer over (no execution) ON<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √<br />

n Table size 1 - 64<br />

B Pointer √ √ √ √ √ √ √ √ √ √ 0 - 63<br />

C Start of table √ √ √ √ √ √<br />

Example<br />

When R011 is ON, the data of XW04 is transferred to the register which is designated by<br />

RW30 in the table D0500 to D0509 (10 registers size).<br />

If the data of RW30 is 8, XW04 data is transferred to D0508.<br />

Source Destination table Pointer<br />

XW04 3210 D0500 0<br />

D0501 1<br />

D0507 7<br />

D0508 3210 8<br />

D0509 9<br />

Note<br />

• If the pointer data designates outside the table (10 or more in the above example), the transfer<br />

is not executed and the output comes ON.<br />

• The table must be within the effective range of the register address.<br />

Basic Hardware and Function 177<br />