7. Instructions<br />

FUN 052 EOR Exclusive OR<br />

Expression<br />

Input −[ A EOR B → C ]− Output<br />

Function<br />

When the input is ON, this instruction finds exclusive OR of A and B, and stores the result in C.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

158 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

B source √ √ √ √ √ √ √ √ √ √ √ √<br />

C Exclusive OR √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When R012 is ON, exclusive OR operation is executed for the data of D1000 and D0300, and<br />

the result is stored in D1000.<br />

If the data of D1000 is H5678 and D0300 is H4321, the result H1559 is stored in D1000.<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

D1000 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0<br />

5 6 7 8<br />

Exclusive OR<br />

D0300 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1<br />

4 3 2 1<br />

D1000 0 0 0 1 0 1 0 1 0 1 0 1 1 0 0 1<br />

1 5 5 9<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net