Special clean area luminaire IP20<br />

67<br />

With low glare specular louvre<br />

Three part luminaire concept<br />

General inform<strong>at</strong>ion<br />

Subject<br />

Chapter<br />

Photometric d<strong>at</strong>a<br />

appendix<br />

Applic<strong>at</strong>ion inform<strong>at</strong>ion appendix<br />

Lighting electronics appendix<br />

Instabus EIB - principles on request<br />

Instabus EIB - components on request<br />

Dimming control<br />

on request<br />

Control gear<br />

appendix<br />

Refurbishment<br />

appendix<br />

Approvals<br />

appendix<br />

Safety markings<br />

appendix<br />

Symbols<br />

appendix<br />

Lamp d<strong>at</strong>a<br />

appendix<br />

Product Index<br />

appendix<br />

C<strong>at</strong>alogue number index appendix<br />

7<br />

Very sensitive or mini<strong>at</strong>ure<br />

components and modern<br />

silicon wafer fabric<strong>at</strong>ion<br />

systems demand a dust and<br />

microorganism free<br />

environment. Employing<br />

laminar-flow technology, with<br />

very low disturbance and low<br />

turbulence within the air<br />

stream, cre<strong>at</strong>es the highest<br />

quality environments. By using<br />

this system any dust particles<br />

are taken out of circul<strong>at</strong>ion<br />

immedi<strong>at</strong>ely. With the very high<br />

air volumes, often in excess of<br />

1620m 3 per hour per m 2 of<br />

ceiling area, the room must be<br />

well designed and with our<br />

specifically designed<br />

luminaires, we can help you to<br />

cre<strong>at</strong>e defect-free production<br />

areas.<br />

Luminaire : 5LJ 165 7-1 CX with 1 x 36W and HFG ( Lumen output : 1 x 3200 lm )<br />

Light output in cd / klm<br />

Tested to DIN 5032<br />

C0 - 1 80 C90 - 270<br />

Total light output r<strong>at</strong>io (LOR) = 56%<br />

Number of luminaires in room<br />

Reflection factors :70/50/20 MF = 0.8<br />

HFG<br />

En [lx] 100 300 500 750<br />

Lh [m] 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0<br />

Floor area A [m 2 ]<br />

20 1. 7 1. 9 5.1 5.6 8.5 9.4 13 14<br />

30 2.4 2.6 7. 1 7. 8 12 13 18 19<br />

40 3. 0 3. 3 9.0 9.8 15 16 22 25<br />

50 3. 6 3. 9 11 12 18 20 27 30<br />

75 5.2 5.5 16 17 26 28 39 41<br />

100 6.9 7. 1 21 21 34 36 52 53<br />

200 13 14 39 41 66 68 98 102<br />

500 32 33 97 98 162 163 243 245<br />

Lh = Luminaire mounting height<br />

Utilis<strong>at</strong>ion<br />

Luminaire utilis<strong>at</strong>ion factors<br />

ρCeiling<br />

80 80 70 70 50 50 30 0<br />

ρWall<br />

50 30 50 30 50 30 30 0<br />

ρFloor<br />

30 10 20 20 10 10 10 0<br />

Room Index k<br />

0.60 29 23 28 24 27 23 23 19<br />

0.80 37 30 35 31 33 30 30 26<br />

1.00 44 37 42 38 39 36 36 33<br />

1.25 48 41 45 42 43 40 40 37<br />

1.50 52 44 49 45 46 43 43 40<br />

2.00 58 49 53 51 50 48 47 45<br />

3.00 62 52 57 55 53 51 50 48<br />

5.00 66 56 60 58 55 54 53 51<br />

Power consumption<br />

Values in W<strong>at</strong>ts<br />

Lamps<br />

HFG<br />

1 x 36W 34<br />

Light distribution to DIN 5040<br />

ϕ u 1. 00<br />

ϕ su 0.60<br />

ϕ so 0.00<br />

Conversion factor F1 for 5LJ 165 .-..<br />

HFG<br />

Conversion factor F for 5LJ 165 .-..<br />

HFG<br />

Classific<strong>at</strong>ion<br />

DIN A 4 0<br />

CIE N1: 62 N2: 96 N3: 100 N 4: 100 N 5: 56<br />

Further photometric d<strong>at</strong>a can be found in our lighting design program SiLICHT