Recessed downlights with advanced light control HIGHLIGHT<br />

37<br />

Secondary beam system<br />

2<br />

Beam reflection schem<strong>at</strong>ics of<br />

the secondary beam system<br />

Electronic gearbox to oper<strong>at</strong>e<br />

HIT lamps<br />

Conventional gearbox to oper<strong>at</strong>e<br />

HIT lamps<br />

Special Fe<strong>at</strong>ures<br />

The luminaires of the type<br />

5NG153… replace the luminaires<br />

5NG151/152. To upgrade<br />

existing install<strong>at</strong>ions with the<br />

new elegant version 5NG153...<br />

an upgrade kit is available which<br />

replaces the old reflector unit<br />

with the new system.<br />

Accessories<br />

Electrical<br />

Code<br />

Electronic transformer<br />

12V, 20 to 80W 5NZ 508 1<br />

12V, 20 to 105W 5NZ 508 4<br />

Emergency E14 on request<br />

Mounting<br />

Concrete casting box<br />

Panel ceiling pl<strong>at</strong>e<br />

Plastered aperture<br />

ceiling ring<br />

Backing pl<strong>at</strong>e<br />

Code<br />

• See page 2/46 for detailed<br />

inform<strong>at</strong>ion<br />

5LR 912 9-0BD<br />

5LR 912 9-4BG<br />

5LR 912 9-0BC<br />

5LR 912 9-0BA<br />

General Inform<strong>at</strong>ion<br />

Subject<br />

Photometric d<strong>at</strong>a<br />

Applic<strong>at</strong>ion inform<strong>at</strong>ion<br />

Lighting electronics<br />

Instabus EIB - principles<br />

Instabus EIB - components<br />

Dimming control<br />

Control gear<br />

Power factor correction<br />

Approvals<br />

Safety markings<br />

Symbols<br />

Lamp d<strong>at</strong>a<br />

Product Index<br />

C<strong>at</strong>alogue number index<br />

Chapter<br />

appendix<br />

appendix<br />

appendix<br />

on request<br />

on request<br />

on request<br />

appendix<br />

appendix<br />

appendix<br />

appendix<br />

appendix<br />

appendix<br />

appendix<br />

appendix<br />

Luminaire : 5NG 153 7-8LM1 with 1 x HIT 150W and HFG ( Lumen output : 1 x 12000 lm )<br />

Light output in cd / klm<br />

Tested to DIN 5032<br />

C0 - 1 80 C90 - 270<br />

Total light output r<strong>at</strong>io (LOR) = 45%<br />

Number of luminaires in room<br />

Reflection factors :70/50/20 MF= 0.8<br />

HFG<br />

En [lx] 100 200 300 500<br />

Lh [m] 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0<br />

Floor area A [m 2 ]<br />

20 0.5 0.5 0.9 1. 0 1. 4 1. 5 2.4 2.5<br />

30 0.7 0.7 1. 4 1. 4 2.1 2.2 3. 4 3. 6<br />

40 0.9 0.9 1. 8 1. 9 2.7 2.8 4.5 4.7<br />

50 1. 1 1. 1 2.2 2.3 3. 3 3. 4 5.5 5.7<br />

75 1. 6 1. 7 3. 2 3. 3 4.8 5.0 8.1 8.3<br />

100 2.1 2.2 4.3 4.4 6.4 6.5 11 11<br />

200 4.2 4.3 8.5 8.5 13 13 21 21<br />

500 10 11 21 21 31 32 52 53<br />

Lh = Luminaire mounting height<br />

Utilis<strong>at</strong>ion<br />

Luminaire utilis<strong>at</strong>ion factors<br />

ρCeiling<br />

80 80 70 70 50 50 30 0<br />

ρWall<br />

50 30 50 30 50 30 30 0<br />

ρFloor<br />

30 10 20 20 10 10 10 0<br />

Room Index k<br />

0.60 34 30 33 31 32 30 30 28<br />

0.80 39 35 38 35 36 34 34 33<br />

1.00 44 39 42 40 40 39 38 37<br />

1.25 46 41 43 42 41 40 40 38<br />

1.50 48 42 45 44 43 42 41 40<br />

2.00 51 44 47 46 44 44 43 42<br />

3.00 53 46 49 48 45 45 44 43<br />

5.00 55 46 50 49 46 45 44 43<br />

Power consumption<br />

Values in W<strong>at</strong>ts<br />

Lamps HFG Switchstart<br />

1 x 1 50W 150 150<br />

Light distribution to DIN 5040<br />

ϕ u 1. 00<br />

ϕ su 0.83<br />

ϕ so 0.00<br />

Conversion factor F1 for 5NG 153 .-..<br />

Conversion factor F for 5NG 153 .-..<br />

HFG<br />

Switchstart<br />

HFG<br />

Switchstart<br />

7-8 LM1 1x 150 W 1. 00 1-8 LM1 1x 150 W 1. 00 7-8 LM1 1x 150 W 1. 00 1-8 LM1 1x 150 W 1. 00<br />

Classific<strong>at</strong>ion<br />

DIN A 7 0<br />

CIE N1: 98 N2: 100 N 3: 100 N 4: 100 N 5: 45<br />

Further photometric d<strong>at</strong>a can be found in our lighting design program SiLICHT