Recessed diffuser luminaire, SiLUZET for ceiling grid or cut aperture<br />

17<br />

with opal or prism<strong>at</strong>ic diffuser<br />

5LJ 443 …, prism<strong>at</strong>ic diffuser 5LS 461… , opal diffuser Diffuser fixings Terminal block<br />

Accessories<br />

Housing<br />

Code<br />

Suction diffuser<br />

removal tool<br />

5LJ 484 0-0XJ<br />

Install<strong>at</strong>ion<br />

For ceilings with<br />

concealed grid or 5LJ 530 0-0XC<br />

concealed support structure<br />

For ceilings with<br />

exposed grid<br />

5LJ 461 1-0XC<br />

• For detailed description see page 8/18<br />

• Dimensions see page 8/19<br />

General inform<strong>at</strong>ion<br />

Subject<br />

Chapter<br />

Photometric d<strong>at</strong>a<br />

appendix<br />

Applic<strong>at</strong>ion inform<strong>at</strong>ion appendix<br />

Lighting electronics appendix<br />

Instabus EIB - principles on request<br />

Instabus EIB - components on request<br />

Dimming control<br />

on request<br />

Control gear<br />

appendix<br />

Power factor correction appendix<br />

Approvals<br />

appendix<br />

Safety markings<br />

appendix<br />

Symbols<br />

appendix<br />

Lamp d<strong>at</strong>a<br />

appendix<br />

Product Index<br />

appendix<br />

C<strong>at</strong>alogue number index appendix<br />

With mounting bracket for<br />

install<strong>at</strong>ion into grid ceilings.<br />

8<br />

Luminaire : 5LJ 444 1-4 AX2 with 4 x 18W and Low-loss ( Lumen output : 4 x 1350 lm )<br />

Light output in cd / klm<br />

Tested to DIN 5032<br />

C0 - 1 80 C90 - 270<br />

Total light output r<strong>at</strong>io (LOR) = 52%<br />

Number of luminaires in room<br />

Reflection factors :70/50/20 MF = 0.8<br />

Low-loss<br />

En [lx] 100 300 500 750<br />

Lh [m] 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0<br />

Floor area A [m 2 ]<br />

20 1. 2 1. 4 3. 7 4.2 6.2 7. 1 9.3 11<br />

30 1. 7 1. 9 5.1 5.8 8.5 9.6 13 14<br />

40 2.1 2.4 6.4 7. 2 11 12 16 18<br />

50 2.6 2.8 7. 7 8.5 13 14 19 21<br />

75 3. 7 3. 9 11 12 18 20 27 29<br />

100 4.8 5.0 14 15 24 25 36 38<br />

200 8.8 9.3 26 28 44 47 66 70<br />

500 22 22 65 65 108 109 162 163<br />

Lh = Luminaire mounting height<br />

Utilis<strong>at</strong>ion<br />

Luminaire utilis<strong>at</strong>ion factors B<br />

ρCeiling<br />

80 80 70 70 50 50 30 0<br />

ρWall<br />

50 30 50 30 50 30 30 0<br />

ρFloor<br />

30 10 20 20 10 10 10 0<br />

Room Index k<br />

0.60 23 18 22 18 21 17 17 13<br />

0.80 29 23 28 23 26 22 22 18<br />

1.00 34 28 33 28 31 27 27 23<br />

1.25 39 31 36 32 34 31 30 27<br />

1.50 43 35 40 36 37 34 33 30<br />

2.00 48 40 45 41 41 39 38 35<br />

3.00 53 44 49 46 45 43 42 39<br />

5.00 59 49 53 51 49 47 46 44<br />

Power consumption<br />

Values in W<strong>at</strong>ts<br />

Lamps<br />

Low-loss<br />

4 x 18W 89<br />

Light distribution to DIN 5040<br />

ϕ u 1. 00<br />

ϕ su 0.52<br />

ϕ so 0.00<br />

Conversion factor F1 for 5LJ 444 .-..<br />

Low-loss<br />

Conversion factor F for 5LJ 444 .-..<br />

Low-loss<br />

Classific<strong>at</strong>ion<br />

DIN A 4 0<br />

CIE N1: 45 N 2: 76 N3: 94 N4: 100 N 5: 52<br />

Further photometric d<strong>at</strong>a can be found in our lighting design program SiLICHT