Appendix<br />

9<br />

Install<strong>at</strong>ion and oper<strong>at</strong>ion guidelines<br />

Maximum HFG ballasts on a single N-breaker, single pole Type B<br />

(Made by Siemens)<br />

HFG : OSRAM Quicktronic QT-S/E and Duluxtronic DT-S/E for Dulux S/E<br />

Breaker Lamp type Switchstart HFG HFG<br />

Size TC-S/TC-SEL PFC 1-lamp 2-lamp<br />

Maximum number of electronic transformers on a single breaker, Type B<br />

(Siemens 5SX…) or Type C (Siemens)<br />

Transformer: Osram Halotronic<br />

Breaker HTM HT HT HT HTM HT HT HT HT<br />

Type 70 70L 70LF 80L 105 105L 120LF 150L 210L<br />

10 A 5W 90 32 –<br />

7W 90 32 –<br />

9W 90 32 20<br />

11W 90 32 20<br />

16A 5W 130 48 –<br />

7W 130 48 –<br />

9W 130 48 28<br />

11W 130 48 28<br />

20A 5W 165 60 –<br />

7W 165 60 –<br />

9W 165 60 34<br />

11W 165 60 34<br />

HFG : OSRAM Quicktronic QT-D/E, QT-T/E and Duluxtronic DT-D/E, DT-T/E for<br />

Dulux D/E and Dulux T/E<br />

Breaker Lamp type Switchstart HFG HFG<br />

Size TC-D/ PFC 1-lamp 2-lamp<br />

TC-DEL<br />

10 A 10W 80 32 20<br />

13W 80 32 20<br />

18W 55 26 20<br />

26W 40 26 20<br />

32W – 20 10<br />

42W – 12 –<br />

16A 10W 118 48 28<br />

13W 118 48 28<br />

18W 88 32 28<br />

26W 66 32 28<br />

32W – 28 16<br />

42W – 18 –<br />

20A 10W 150 60 34<br />

13W 150 60 34<br />

18W 110 48 34<br />

26W 82 48 34<br />

32W – 34 20<br />

42W – 22 –<br />

Maximum OSRAM Powertronic ballasts for discharge lamps on a single breaker<br />

Type B or Type C (made by Siemens)<br />

10A 37 37 37 19 23 15 13 8 5<br />

B 16A 59 59 59 30 38 24 21 13 9<br />

B 20A 74 74 74 38 47 30 27 16 11<br />

B 25A 92 92 92 47 59 38 34 26 14<br />

C 10A 37 37 37 27 23 21 20 14 9<br />

C 16A 59 59 59 43 38 34 32 22 15<br />

C 20A 74 74 74 54 47 43 40 28 19<br />

C 25A 92 92 92 67 59 53 50 34 24<br />

Faults in infra-red control / transmission equipment<br />

Fluorescent lamps emit radi<strong>at</strong>ion in the frequency range which is<br />

also used by infra-red transmission. IR-receivers are often not<br />

selective, so the IR-equipment can be disturbed. The light which is<br />

emitted by the lamp, is modul<strong>at</strong>ed with the high oper<strong>at</strong>ing<br />

frequency (20-50kHz). It may cause interference with signals in<br />

the same frequency range.<br />

IR remote control:<br />

Trouble free oper<strong>at</strong>ing is possible with equipment which works<br />

with sufficiently high carrier frequencies (400-1500kHz).<br />

Audio transmission:<br />

The carrier signal for audio transmission until now has been in<br />

the frequency range 95kHz and higher, so th<strong>at</strong> the 3th , 5th and<br />

7th harmonics from the HFG oper<strong>at</strong>ing frequency ranges (30kHz<br />

to 45kHz normal, dimming up to 100kHz) have caused<br />

considerable interference with transmissions. The transition of<br />

headphone manufacturers to higher frequency ranges, e.g. 2,3<br />

MHz and 2,8 MHz, has brought about a solution. Generally, it is<br />

recommended to miss out the first 6 transmission channels, in<br />

particular channel 1 because they, are more susceptible to be<br />

disturbed by harmonics of basic HFG frequencies.<br />

appendix<br />

Breaker type PTU70/230-240 PT150/230-240 N-2 PT-DS 80/230-240<br />

B 10A 10 5 8<br />

B 16A 15 8 12<br />

B 20A 20 10 15<br />

B 25A 25 12 20<br />

C 10A 20 10 8<br />

C 16A 30 16 12<br />

C 20A 40 20 15<br />

C 25A 40 25 20