Configuring Intrusion Zones with AntipassbackConfiguring Intrusion Zones with AntipassbackTo configure a door that is also part of an antipassback area, display the DoorTab, and use the horizontal scroll bar in the Doors Selected area to displayDirection.Figure 12-7 on page 12-31 shows an intrusion zone that is also an antipassbackarea.Figure 12-7: iSTAR Intrusion Zone with AntipassbackIn Figure 12-7 on page 12-31, the AP areas are created before the intrusionzone. AP 52 includes a middle door with reader 3 as the inbound reader to AP52 and reader 4 as the outbound reader from AP 52 to AP 51. All exit doors toan area can be configured as arming or disarming points to the intrusion zone.Designating a door as an OUT door reverses the actions and effects of thedoor strike and the DSM.C•CURE <strong>800</strong>/<strong>800</strong>0 <strong>Software</strong> <strong>Configuration</strong> <strong>Guide</strong> 12–31