<strong>ITALY</strong> - 4 Wastewater<br />

Table 4.1.2-b. Required Systems in the Tuscany Region for the Treatment of Domestic and<br />

Urban Wastewater Generated by Installations less than 10,000 IE and Discharging to Sea Water<br />

Quality of Sea Water Normal<br />

Sensitive<br />

Area<br />

Inhabitant Equivalents (IE) < 10,000<br />

Treatment systems A B<br />

Septic tank (two-stage, three stage or Imhoff) and fine screen and offshore<br />

conduit<br />

X<br />

Septic tank (two-stage, three stage or Imhoff) and percolating filter or<br />

activated sludge or biodisc filter<br />

X<br />

Septic tank (two-stage, three stage or Imhoff) and prolonged venting X<br />

system<br />

Primary treatment and OX-ANOX system X<br />

Biological plant and phytopurification X<br />

Biological plant and pond or clariflocculation (1) X<br />

Alternate cycles process X X<br />

Notes:<br />

(1) The use of ponds or lagoons shall be approved. All permits shall be obtained through the Italian Base<br />

Commander.<br />

Table 4.2-a. Monitoring Frequency for Discharges of Urban Wastewater<br />

Plant Capacity (in IE) # of Samples (1)<br />

All other<br />

Regions<br />

Veneto<br />

Region<br />

Tuscany<br />

Region<br />

All other Regions Veneto Region Tuscany Region<br />

1 to 1,999 From<br />

threshold<br />

values (2) 501 to 2000 None specified 2 samples during the<br />

2<br />

first year e 1 sample<br />

to<br />

every 2 years, if in<br />

1,999<br />

compliance; if one of<br />

the samples is not in<br />

compliance, 1 sample<br />

shall be collected in<br />

the following year.<br />

2,000 to 9,999 2,001 to 12 samples during the first year and 4 samples/year thereafter, if in<br />

10,000 compliance; if one of the 4 samples is not in compliance, 12 samples<br />

shall be collected the following year<br />

10,000 to 49,999 10,001 to<br />

49,999<br />

12 samples/year<br />

> 50,000 24 samples/year<br />

Notes:<br />

(1) The column specifies the minimum annual number of samples. Samples shall be taken at regular intervals<br />

during the year. An equal number of self-monitoring samples shall be collected by the manager of the<br />

wastewater treatment plant from both influent and effluent.<br />

(2) See Table 4.1.1-b<br />

September 2012 Italy FGS 4-32<br />