<strong>ITALY</strong> - 3 Drinking Water<br />

Contaminant<br />

Table 3.4-b. Inorganics Monitoring Requirements (Purchased Water)<br />

Groundwater<br />

Baseline<br />

Requirement 1<br />

Surface Water<br />

Baseline<br />

Requirement<br />

Trigger That<br />

Increases<br />

Monitoring 2<br />

Reduced<br />

Monitoring<br />

Arsenic 1 sample / 3 yr Annual sample >MCL ---<br />

Antimony 1 sample / 3 yr Annual sample >MCL ---<br />

Barium 1 sample / 3 yr Annual sample >MCL ---<br />

Beryllium 1 sample / 3 yr Annual sample >MCL ---<br />

Cadmium 1 sample / 3 yr Annual sample >MCL ---<br />

Chromium 1 sample / 3 yr Annual sample >MCL ---<br />

Cyanide 1 sample / 3 yr Annual sample >MCL ---<br />

Fluoride 1 sample / 3 yr Annual sample >MCL<br />

Mercury 1 sample / 3 yr Annual sample >MCL ---<br />

Nickel 1 sample / 3 yr Annual sample >MCL ---<br />

Selenium 1 sample / 3 yr Annual sample >MCL ---<br />

Thallium 1 sample / 3 yr Annual sample >MCL ---<br />

Sodium 1 sample / 3 yr Annual sample --- ---<br />

Asbestos 3 1 sample every 9 1 sample every 9 >MCL Yes<br />

years<br />

years<br />

Total<br />

Annual sample Quarterly >50% Nitrite ---<br />

Nitrate/Nitrite<br />

MCL 4<br />

Nitrate Annual sample Quarterly >50% MCL 5 Yes 6<br />

Nitrite Annual sample Quarterly >50% MCL 5 Yes 7<br />

Corrosivity 8 Once Once --- ---<br />

Notes:<br />

1. Samples shall be taken as follows: groundwater systems shall take a minimum of one sample at every entry<br />

point to the distribution system which is representative of each well after treatment; surface water systems<br />

shall take at least one sample at every entry point to the distribution system after any application of<br />

treatment or in the distribution system at a point which is representative of each source after the treatment.<br />

2. Increased quarterly monitoring requires a minimum of 2 samples per quarter for groundwater systems and<br />

at least 4 samples per quarter for surface water systems.<br />

3. Necessity for analysis is predicated upon a sanitary survey conducted by the PWS.<br />

4. Any sampling point with an analytical value ≥ 0.075 mg/L as N, (50% of the Nitrite MCL) must begin<br />

sampling for nitrate and nitrite separately. Since nitrite readily converts to nitrate, a system can conclude<br />

that if the total nitrate/nitrite value of a sample is less than half of the nitrite MCL, then the value of nitrite<br />

in the sample would also be below half of its MCL.<br />

5. Increased quarterly monitoring shall be undertaken for nitrate and nitrite if a sample is >50% of the MCL.<br />

6. The appropriate DoD medical authority may reduce repeat sampling frequency for surface water systems to<br />

annually if after 1 year results are