<strong>ITALY</strong> - 3 Drinking Water<br />

Table 3.4-a. Inorganics Monitoring Requirements (DoD-Produced Water)<br />

Parameter<br />

Frequency<br />

(See Table 3.5-a)<br />

Note<br />

Aluminum Check Monitoring Necessary only when used as flocculants<br />

or present, in significant concentration, in<br />

the drinking water source utilized<br />

Ammonium Check Monitoring<br />

Antimony Audit monitoring<br />

Arsenic Audit monitoring<br />

Asbestos 1 sample every 9<br />

years<br />

Barium 1 sample every 3<br />

years<br />

Beryllium 1 sample every 3<br />

years<br />

Boron Audit monitoring<br />

Bromate Audit monitoring<br />

Cadmium Audit monitoring<br />

Chlorides Audit monitoring<br />

Chlorite Audit monitoring<br />

Chromium Audit monitoring<br />

Copper Audit monitoring<br />

Conductivity Check Monitoring<br />

Cyanide Audit monitoring<br />

Dry Residues at<br />

180°C<br />

Audit monitoring<br />

Necessity for analysis is predicated upon<br />

a vulnerability assessment conducted by<br />

the PWS<br />

The frequency must be increased to an<br />

annual sample if water is produced from<br />

Surface Water<br />

The frequency must be increased to an<br />

annual sample if water is produced from<br />

Surface Water<br />

Fluoride Audit monitoring Daily monitoring is recommended for<br />

systems practicing fluoridation (see Table<br />

3.10 for fluoridation criteria)<br />

Hydrogen ion<br />

concentration<br />

Check Monitoring<br />

Iron Check Monitoring Necessary only when used as flocculant<br />

or present, in significant concentration, in<br />

September 2012 Italy FGS 3-20<br />

Revision 0