<strong>ITALY</strong> - 19 Underground Storage Tanks<br />

C19.3.5. Deferred USTs. Deferred USTs constructed after 8 May 1985 must be designed<br />

and constructed with corrosion protection, non-corrodible materials, or be otherwise designed<br />

and constructed to prevent releases from corrosion or structural failure. UST materials must be<br />

compatible with the substance(s) to be stored.<br />

C19.3.6. Identification Tags for USTS Installed at Fuel Filling Stations<br />

C19.3.6.1. The maximum storage capacity of POL USTs installed at fuel filling stations<br />

is 50 m 3 (1,765 ft 3 ). POL USTs installed at fuel filling stations shall have an identification tag<br />

with the following information:<br />

C19.3.6.1.1. Name and address of the UST manufacturer<br />

C19.3.6.1.2. Year of construction<br />

C19.3.6.1.3. Storage capacity, wall thickness, and construction material(s)<br />

C19.3.6.1.4. UST operating pressure and operating pressure of the interstitial space<br />

C19.3.7. Minimum Distance for USTS from Drinking Water Supply Wells. USTs for POL<br />

and/or hazardous materials shall be at least 200 meters (656 feet) from any drinking water supply<br />

well. Refer to Chapter 3, “Drinking Water.”<br />

September 2012 Italy FGS 19-5<br />

Revision 0