<strong>ITALY</strong> - 19 Underground Storage Tanks<br />

C19.2.6.1. Tanks containing heating oil used for consumption on the premises where it is<br />

stored;<br />

C19.2.6.2. Septic tanks;<br />

C19.2.6.3. Stormwater or wastewater collection systems;<br />

C19.2.6.4. Flow through process tanks;<br />

C19.2.6.5. Surface impoundments, pits, ponds, or lagoons;<br />

C19.2.6.6. Field constructed tanks;<br />

C19.2.6.7. Hydrant fueling systems;<br />

C19.2.6.8. Storage tanks located in an accessible underground area (such as a basement<br />

or vault) if the storage tank is situated upon or above the surface of the floor;<br />

C19.2.6.9. USTs containing de minimis concentrations of regulated substances, except<br />

where C19.3.2.8. is applicable; and<br />

C19.2.6.10. Emergency spill or overflow containment UST systems that are<br />

expeditiously emptied after use.<br />

C19.3. CRITERIA<br />

C19.3.1. All installations will maintain a UST inventory.<br />

C19.3.2. POL USTs. All petroleum UST systems will be properly installed, protected from<br />

corrosion, provided with spill/overfill prevention, and will incorporate leak detection as<br />

described below. POL USTs installed at fuel filling stations will either be double-walled or have<br />

a secondary containment vault.<br />

C19.3.2.1. Corrosion Protection. USTs and piping must be provided with corrosion<br />

protection unless constructed of fiberglass or other non-corrodible materials. The corrosion<br />

protection system must be certified by a competent authority.<br />

C19.3.2.1.1. Fuel Filling Stations. Double-walled USTs installed at fuel filling<br />

stations shall have walls constructed of one of the following:<br />

C19.3.2.1.1.1. Both metallic, with the external surface coated with an anticorrosion<br />

layer<br />

C19.3.2.1.1.2. Metallic internal surface and non-metallic external surface<br />

C19.3.2.1.1.3. Both non-metallic surface if the wall material is both resistant to<br />

corrosion and to mechanical stress<br />

September 2012 Italy FGS 19-2<br />