BASES<br />

APPLICATION<br />

TO SAFETY<br />

ANALYSIS<br />

(CONT.)<br />

LCO 3.1<br />

The Automatic Sprinkler System provides a credited safety function to suppress<br />

postulated fires occurring in the BUILDING 991 COMPLEX Office Areas and<br />

reduce the likelihood that Office Area fires will impact waste container storage<br />

areas The Automatic Sprinkler System is expected to actuate automatically and<br />

mitigate the Office Area fire to prevent fire propagation into contiguous waste<br />

container storage areas. The Automatic Sprinkler System also provides a credited<br />

safety function to mitigate the effects <strong>of</strong> any fires that may occur in waste<br />

container storage areas. An additional safety function is provided by the Flow<br />

Alarm Transmittal System which notifies the Fire <strong>Department</strong> <strong>of</strong> Automatic<br />

Sprinkler Svstern actuation, initiating Fire <strong>Department</strong> response to extinguish the<br />

fire and mitigate any fire related impacts. The Smoke Detection Alarm<br />

Transmittal Smem arovides a svstern to detect and reoort fircs non-sr>rinklered<br />

waste stowe anas <strong>of</strong> the BUILDING 991 COMPLEX to facilitate response <strong>of</strong> the<br />

Fire Demrtnient. Receipt <strong>of</strong> the dann from the Smoke Detection Svsteni will<br />

initiate Fire <strong>Department</strong> response to extinwish the fix and mitigate anv fire<br />

related imDacts. ReceiDt <strong>of</strong> the alm from the Smoke Dctechon Svstem will also<br />

facilitale initiation <strong>of</strong> an LS/DU' announcement to notifk personnel inside<br />

Building 991 <strong>of</strong> the fire.<br />

The BUILDING 991 COMPLEX Automatic Sprinkler System and Flow:'Smoke<br />

Detection Alarm T&mittal Systems shall be OPERABLE.<br />

For the Automatic Sprinkler System to be OPERABLE, the system must be<br />

capable <strong>of</strong> automatidy supplying water to waste container storage areas and the<br />

Office Area <strong>of</strong> the BUILDING 991 COMPLEX sufficient to suppress fire growth<br />

in those areas following the initiation <strong>of</strong> fires with significant growth potential<br />

For the Flow Alarm Transmittal System to be OPERABLE, the system must be<br />

capable <strong>of</strong> detecting Automatic Sprinkler System use and providing a signal to the<br />

Fire Dispatch Center andor the Central Alarm Station. For the Smoke Detection<br />

Alarm Transn~ttai System UJ be OPEWLE. the system must be wable <strong>of</strong><br />

deteminrr a fire and Drovidina a simal to the Fir6 Disuatch Center an&'or Central<br />

Alann Station.<br />

~~ ~~<br />

APPLICABILITY This LCO is applicable to those portions <strong>of</strong> the BUILDING 991 COMPLEX that<br />

are waste container storage areas @e., Budding 991 waste container storage areas,<br />

Building 998 (Room 300 and Corridor A), the Building 991 West Dock Canopy<br />

Area, . Suildint. 996. and the Building 991 East Dock Canopy Area) and is I<br />

applicable to the BUILDING991 COMPLEX Office Area. The LCO is<br />

applicable at all times.<br />

Revision 1<br />

September 1999<br />

~~<br />

A-29 Building 991 Complex FSAR<br />

Appendix A<br />

~