EMCClE-9<br />

Table 2-4 Loads on Diesel Generator<br />

EMCC I Load<br />

EMCClA-3 I Lighting Transformer. 30 kVA. 480 V-12Of208 V<br />

Breathing Air Receptacle<br />

Welding Receptacle<br />

Instrument Air Comuressor<br />

Vacuum Pump P601B<br />

Pit Sump Pump P601<br />

Transfer Pump P602<br />

Vacuum Pump P601A & P601B<br />

Building 985 Smlv Fan F602<br />

Plenum Exbaust Fan F601A<br />

Plenum Exhaust Fan F601B<br />

Health Phvsics Air Sam~lers<br />

EMCClD-4<br />

Lighting transformer, 30 kVA 480V-12Of208V<br />

Breathbe Air ReceDtacle<br />

Welding Receptacle ~<br />

Instrument Air Compressor, AC-601<br />

Pit sum^ PUmD P601<br />

Transfer Pmnp P602<br />

Vacuum Pum~ P601A & P601B West<br />

Hot Water circulation Pump, P604A West<br />

Hot Water circulation Pump, P604B East<br />

Buildine; 985 Smlv Fan. F602<br />

Plumm Exhaust Fan F601A<br />

Plumm Exhaust Fan F60 1B<br />

Health Physics Vacuum Pump A<br />

Health Physics Vacuum Pump B<br />

Vacuum Pump<br />

Plenum Exhaust Fan #1<br />

Plenum Exhaust Fan #2<br />

Plenum Exhaust Fan #3<br />

15 kVA Panel<br />

I 25 kVA Panel 1<br />

L I<br />

Genexator Building 989<br />

Air sampling system .<br />

I I circulating Pump P-5 1<br />

A fire water holding tank is located in a pit at the east end <strong>of</strong> Building 985. The tank IS<br />

designed to collect the drains from the exhaust plenum in the event the plenum fire sprinklers are<br />

activated. If water is introduced into this tank, Waste Management is contacted for assistance ui<br />

the disposal <strong>of</strong> the water. The system has a recirculating system for sampling the water and a<br />

pump that discharges to a hose connection by the east door <strong>of</strong> the building. By utilizing the<br />

pump and hose connection the contents could be transferred to a mobile tank by hose and<br />

transported to a disposal site. The fire water holding tank does not contain Raschig rings In<br />

addition to the plenum drains, a sump pump in the fire water holding tank also discharges to the<br />

tank.<br />

Revision 1<br />

Building 991 Complex FSAR<br />

Scptcmher 1999 I<br />

~<br />

~