17.06.2013 Views

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

system contains an untested HEPA stage on the ro<strong>of</strong> where the exhaust fan is located.<br />

Building 998 is exhausted by exhaust system E-18.<br />

Buildings 996, 997 and 999 and Corridors B and C are exhausted by the Building 985<br />

filter plenum. This system also draws some air from the north side <strong>of</strong> Building 991. If th~s<br />

system is inoperable, it is expected that air from these buildings and conidors would be<br />

exhausted by the Building 991 plenum exhaust fans. The door located in Corridor B would<br />

probably have to be left open to obtain an adequate flow from the buildings.<br />

Room 134 has no dedicated filtration system. Depending on the configuration <strong>of</strong> the<br />

building (e.g., roll-up doors between Rooms 170 and 134 and Rooms 170 and 140/141 left open;<br />

supply system S-1 in Room 130 door left open; installation <strong>of</strong> fire doors between the <strong>of</strong>fice area<br />

and Room 134, etc.) air may either exhaust into or out <strong>of</strong> the room. Possible exhaust paths for<br />

the air in Room 134 are through an exhaust duct located in Room 132 (exhaust system E-4) and<br />

one located in Room 135 (probably exhaust system E-20). The airlock doors in the north-south<br />

running hallway have been removed. which ensures a dedicated flow path for Room 134 into the<br />

north portion <strong>of</strong> the buildinp no matter the conficzuration <strong>of</strong> the roll-up doors. Therefore. air in<br />

Room 134 is expected to be exhausted by the Building 991 exhaust filtration svstem.<br />

Room 170, the west dock, has no dedicated filtration system. Good air flow was noted<br />

from Room 170 into Rooms 140/141 through the fire doors. The future modification plans <strong>of</strong><br />

the building include installing a fire-rated roll-up door between these rooms with smoke<br />

detectors. The plan is to keep this door normally open but this cannot be guaranteed. If the door<br />

remains open, and if the Building 991 ro<strong>of</strong> plenum exhaust fans are operating, air from<br />

Room 170 could be exhausted through the north building exhaust ducts. If the door is closed,<br />

either intentionally or because the heat detectors automatically close the door, and if other flow<br />

paths to the north Dodon <strong>of</strong> the building are blocked, the air probably will not be exhausted<br />

through a HEPA fitration system.<br />

Room 166 has no dedicated filtration system. Air in this room does not exhaust through<br />

a HEPA fitration system.<br />

The <strong>of</strong>fice area, Rooms 101 through 129, have no dedicated filtration systems except for<br />

the exhaust fan for the women’s bathroom and locker room. This exhaust system feeds the<br />

Building 991 ro<strong>of</strong> plenum exhaust system. An exhaust system (E-8) is located in Room 101 but<br />

the system is not operational. This exhaust system also feeds the Building 991 ro<strong>of</strong> plenum<br />

exhaust system. During the summer months, operation <strong>of</strong> the return air fan does fhction LO<br />

exhaust portions <strong>of</strong> the <strong>of</strong>fice area. This system exhausts directly to the atmosphere. Two other<br />

exhaust systems are located in Room 110. These systems, when operational, exhaust directly to<br />

the atmosphere.<br />

An engheerk evaluation (Ref. 26) concluded that the south waste stora9e areas<br />

[Rooms 134, 147 and 170) should be considered HEPA filtered and that Room 166 should be<br />

considered an unfiltered area. This evaluation recommended that a permanent differexxi a1<br />

pressure gage be located in Room 170 to measure the differential Dressure in this room with<br />

resDect to an atmosoheric reference. The evaluation aiso recornmended that exhaust t7nn E-11<br />

Revision 1 2-44<br />

Scotemher 1999<br />

Building 99 1 Complex FSAR<br />

I

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!