17.06.2013 Views

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Table 2-1 Fire Suppression Systems and Coverage<br />

System<br />

System A (riser located in basement)<br />

I Coverage<br />

F<br />

I hsement<br />

E3uilding 991 Waste Storage keas<br />

Supply to the East Dock and Building 989 dry pipe<br />

I<br />

System B (riser located in Room 170 - West Dock)<br />

Building 985 riser<br />

- Y<br />

Uu hose valves in these arm<br />

Supply to the West Dock and Canopy area<br />

Building 985<br />

EIuilding 985 filter plenum deluge system<br />

All hose valves in Building 985.<br />

There are two accessible fire hydrants located within 75 feet <strong>of</strong> Building 991 <strong>of</strong> the<br />

Building 991 Complex and one located within 75 feet <strong>of</strong> Building 985. See Figure 2-10 for the<br />

Building 991 Complex for the fire protection water loop with hydrant locations. These hydrants<br />

are identified as Hydrants 9-3, 9-4 and 9-5. Hydrant 9-3 is located directly west <strong>of</strong> Building 985<br />

on the west side <strong>of</strong> the north-south running road and provides access to pump into the sprinkler<br />

system and standpipe Fire <strong>Department</strong> connections located on the south side <strong>of</strong> Building 985.<br />

Hydrant94 is positioned near the southwest corner <strong>of</strong> Building991 and provides access to<br />

pump into the sprinkler system and standpipe Fire <strong>Department</strong> connections located on the west<br />

side <strong>of</strong> the building and also provides access to Building 992 and Building 984. Buildings 996,<br />

997 and 999 could also be supported by this hydrant or they could be accessed from within<br />

Building 99 1. Hydrant 9-5 is located near the southeast comer <strong>of</strong> Building 991 and is in a useful<br />

position for interior attack <strong>of</strong> the Building 991 <strong>of</strong>lice areas, mechanical rooms, basement, and<br />

waste storage areas in Rooms 134 and 166, and Buildings 989 and 984. These fre hydrants<br />

provide adequate coverage <strong>of</strong> the complex.<br />

2.3.1.2 Automatic Sprinkler System<br />

Portions <strong>of</strong> Buildiog 991, Building 998, and the basement level are protected by an<br />

overhead automatic wet-pipe sprinkler system, designated as System A. Building 985 is also<br />

protected by an overhead automatic wet-pipe sprinkler system. The wet-pipe sprinkler systems<br />

were installed to an Ordinary Hazard pipe schedule per NFPA 13. The “Ordinary Hazard”<br />

classification requires a minimum residual pressure <strong>of</strong> 20pounds per square inch (psi) plus<br />

elevation to the highest sprinkler (approximately :27 psi for Building 991) and a required flow<br />

rate at the base <strong>of</strong> the riser <strong>of</strong> 850 to 1500 gallons per minute (gpm). Per the FHA (Ref. 24), the<br />

available pressure and flow rates for the sprinkler systems in Building 991 exceed the required<br />

minimum for pipe schedule systems: (1) for Ordinary Hazard Group 1 occupancy under the<br />

1989 edition <strong>of</strong> NFPA 13, and (2) for Ordinary Hazard occupancy under the 1994 edition <strong>of</strong><br />

NFPA 13.<br />

Building 99 1 Complex FSAR

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!