SURVEILLANCE REOUIREISfEXTS BASES<br />

SR421 fie mnibination <strong>of</strong> a working shift and activitt coinoletion sun.cilIancc 15<br />

(continued) suficient rather dim a continuous sunreillance due to the twe <strong>of</strong> actnitiq:<br />

conducted in the BUILDKG 991 COMPLEX Since the nomial opr'rahons <strong>of</strong> the<br />

faciliW do not deal with exoosed radioactive rnaterhls (LE . mdioamve niatenals<br />

are in nietal containen.). iiltered exhaust is not ~iecessan. for coritarniriacion<br />

control. The Filtered Exhaust Ventilation Svstem provides mitigatioti for<br />

pomlatcd accidents. The combination <strong>of</strong> the reliabiiitv <strong>of</strong> the svstem, the lack <strong>of</strong><br />

contamination in the hili@. the likelihood <strong>of</strong> accidents resulting in radioacme<br />

material releases during, a working shift and the vefification <strong>of</strong> configuntiot:<br />

restoration following receivinrr and shipping activities ii~stifv the acceptabilih <strong>of</strong> a<br />

working shift vcrsus a continlious surveillance. If SR 4 2 3 is not met. enm into<br />

LCO COYDITION E is exuected.<br />

SR 4.2.5 The verification that the uressure differential across the Buildino 991 ventilruioii<br />

svstem exhaust plenum is below a mcified limit assures, in uart. the<br />

OPERABILITY <strong>of</strong> the Filtered Exhaust Vcntiladon System. The SR to venfL<br />

p~enuin differential ~ressure each workina shift Drovides an indicafon that the<br />

plenum single stage <strong>of</strong> HEPA filtration is unblocked. "lie working shift<br />

sunveillance is sufficient. rather than a continuous surveillance due to likelihood <strong>of</strong><br />

events occurring &ax would yield blocked filters. Events <strong>of</strong> the me necessary to<br />

Geld conditions that would fil the SR are si~ficant events in the faciliti and<br />

their impact on the stage <strong>of</strong> HEPA fif.tration is likelv to be investigated follo\\inq<br />

the event occurrence. If SR 4.2.5 is not met. entrv into LCO COKDTTIOU F IC<br />

expected.<br />