3J4. LIILlXTfNG CONDXTlUKS FOR OPERATXON AND SURVEILLANCE<br />

REO UPREMENTS<br />

3.3 LII~~~TING cowmrox FOR OPERATION: Buumw 992 COMPLEX<br />

AUTOMATIC PLENLTM DELUGE SYSTEMS<br />

LCO: The RUILDIXG 991 COMPLEX Automatic Plenum Deluge Svstens Sh-aA<br />

ne OPERABLE, With The Following:<br />

APPLICA321LITY:<br />

CONDITION<br />

A. Automatic Plenum Delune<br />

System in the<br />

Building 991 plenum not<br />

OPER43LE.<br />

B. Automatic Plenum Deiuge<br />

Svstem in the<br />

Building 985 plenum not<br />

OPERABLE.<br />

Revision 1.<br />

Swtcmher 1990<br />

1. The Building 991 exhaust ventilation svsteni Dienum shall have a deluge<br />

system composed <strong>of</strong> heat detectors, automatic deluge actuation, and manual<br />

operation cambilitv.<br />

2. The Building985 exhaust ventilation system plenum shall have a deluge<br />

svstem composed <strong>of</strong> heat detectors. automatic deluge actuation. and manual<br />

operation cavabiiitv, if the exhaust ventilation system is intended to be used<br />

At all times in the Building 991 Filtered Exhaust Ventilation System<br />

plenum and in the Building 985 Filtered Exhaust Ventilation System<br />

plenum if the Buildinn 985 ventilation system is intended to be used<br />

A4. 1<br />

REOUIRED ACTION<br />

Terminate ail hot work in<br />

AFFECTED AREL4S.<br />

- AND<br />

A.2 Restore Automatic Plenum<br />

Deluge System<br />

B. I<br />

- OR<br />

OPEFUBELITY.<br />

Stop operation <strong>of</strong> the<br />

Building 985 exhaust<br />

ventilation svstem main<br />

exhaust fans.<br />

B.2.1 Terminate all hot work in<br />

AFFECTED AREAS.<br />

AND<br />

B.2.2 Restore Automatic Plenum<br />

Deluge Svsteni<br />

OPERM3ILITI’.<br />

COhCLETIOX TIME<br />

2 hours.<br />

45 daw.<br />

3 hours.<br />

2 hours.<br />

45 dam.<br />

A-62 Buildmg 991 Complex FShR<br />

Appendix A