AOL 7<br />

BASIS<br />

(cont'd)<br />

AOL 8<br />

BASIS:<br />

Revision 1<br />

Sepbmher 1993<br />

In order to assure that upper tier waste containers (3& and 4* tiers) are banded in the<br />

BUILDING 991 COMPLEX, a general verification <strong>of</strong> the banding is specified for<br />

identification <strong>of</strong> non-banded upper tier waste containers during facility operations<br />

and tours. This verification is only expected to observe upper tier waste containers<br />

while personnel pass through the facilities or perform activities in the facilities.<br />

This AOL applies to POC and waste containers that are to be stored in the<br />

BUILDING 991 COMPLEX and waste that may be cenerated it1 Building 985 This 1<br />

AOL also applies to SNM containers that are to be staged in the BUILDING 991<br />

COMPLEX. The term "south waste container storage areas-' will be used 111 the<br />

following discussion to sipJiifv Rooms 134. 135, 147, and 170. The term does riot<br />

atmft; to Room 166, Corridor A, Roam 300. Corridor B, Building 996. or the north<br />

waste container storage areas in Building 991 (ie.. Rooms 140/141, 142. 143, 138.<br />

151, 155. 158, and the hallwall north <strong>of</strong> Room I40/141).<br />

The FSAR Safety Analysis made the following assumptions dealing with contamer<br />

operations controls:<br />

Filtered exhaust ventilation is available in Rooms 134 and I35 as long as the<br />

proper airflow connection to the north waste storage area is maintained ProDer<br />

airflow connection consists <strong>of</strong>:<br />

1. The airlock doors s~arating Room 133 from the. north waste storane area are b~m.<br />

- OR<br />

2.1 The roll-w door bemeen Room 1-2 and I70 is own.<br />

2.2.1 The door between Rooms 170 and 140/141 is open.<br />

- OR<br />

2 2.2 The door between RQO~S 170 and 147A is open<br />

A-I20 Building 991 Complex FSAR 1<br />

Appendix 4 [