BASES<br />

APPLICATION<br />

TO SAFETY<br />

ANALYSIS<br />

The Automatic Plenum Deluge Svstems supnort the Filtered Exhaust Ventilatiori<br />

Svstenis bv providing protection <strong>of</strong>the HEPA filters diirhg resyonsc to fires. 7122<br />

FEVS is a recognized control credited to mitigate the public and collocated worker<br />

radiolorjcal dose conseaumces for several dominant Dosculattd accident scenaios<br />

as indimd in Chwter 5. ,krfetv Stnicfiires, Swtenls. aid Cumrionenfs. <strong>of</strong> the<br />

FSAR. 71rc control was not credited as uart <strong>of</strong> the accident andvsis presented in<br />

the FSAR-suu~ortinn Nuclear Saiktv Teclrnical Report fiSTR). Rather. the<br />

control was identified and crcdited as art <strong>of</strong> the dominant accident scenario<br />

discussions in the NSTR and in Chapter 4. Hazard and Accidmzt Anrrlwzs<br />

Summan- <strong>of</strong> the FSAR. The single stage <strong>of</strong> HEPA filtration is credited with<br />

accident scenario mitigation for most operational event scenarios.<br />

-<br />

The Autoniatic Plenum Deluge Svstems are a DEFEYSE-IN-DEPTH mitivative<br />

feature for filter Drotection in remonse to lme faciliw fires. IXe internal facility<br />

fires evaluated in the s d i analyses onlv deal wirh 1 MW and 2 hlu’ fires which<br />

mill not challenve the ventilation srstems and filters. Laz cr fires would have to<br />

occur in order to reach plenum temperatures in excess <strong>of</strong> 19W’F and achmte the<br />

Autotnatic Plenum Deluw Svstems. A potential docs esist for hot embers and<br />

flvinrr brands from analvzcd fires to be cautured bv the filters and create the<br />

potential for filter imition. but the likelihood <strong>of</strong> this event is considered to be low.<br />

In this situation. the deluw system would onlv be actuated rnanuallv and onlv if<br />

filter imition was observed or felt to be imminent. and the filter mxxtinrfloss issut?<br />

would influence the decision to use the svstem. Therefore- the likelihood <strong>of</strong> the<br />

actuation <strong>of</strong> this svstem. either automaticaZfv or mmdlv. is considered to be low<br />

As such. the systcrn is not credited in the safh analyses and onlv serve as a<br />

DEFEME-LV-DEPTH mitigative feature for a uotential mitigation <strong>of</strong> low<br />

likelihood events.<br />

LCO 3.3 The BUILDING991 COMPLEX Automatic Plenum Deluge Svstenis shall be<br />

OPER4BLE.<br />

Revision I<br />

Septcmkr 1990<br />

For the Automatic Plenum Deluge Svstems to be OPERABLE. the ststenis mus?<br />

be CaDable <strong>of</strong> automaticallv or nianuallv suoulvino cooling and/or pietting water<br />

mray inside the W S olenums. The svmms must be cauable <strong>of</strong> detecdino hi&<br />

temuemtures in a vzntilation svstem Dlenum and automaticallv openine a delu~e<br />

svsteni salve. The systems must dso provide a capabilitv <strong>of</strong> ~i‘muall~ bwassing<br />

the automatic deluge dve and <strong>of</strong> manuallv acttiatinr the filter direct sumv portion<br />

<strong>of</strong> the svstem.<br />

A-67<br />

Building 991 Complex FSAR<br />

Appendix A<br />

I