17.06.2013 Views

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

closure project manager - Document Request - U.S. Department of ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Pump<br />

P-7<br />

Configuration<br />

This pump supplies the preheat coils on S-1, S-2, S-3, S-4 and S-5. P-7 is controlled by an<br />

outside air sensor (T-21) located on the north wall <strong>of</strong> Room 137. T-21 will star& P-7 at an<br />

outside temperature <strong>of</strong> less than 70°F.<br />

Due to the many alterations to Building 991 over the years there is duplication in<br />

equipment numbering. The pumps numbered P-1 through P-7, as discussed above, are all<br />

located in Room 137 along the south and west walls. The preheat coil pumps, numbers P-1<br />

through P-5 and discussed in Section 2.3.2.1, are all located by their respective supply plenums.<br />

On loss <strong>of</strong> normal power, pumps P-5 and P-7 in Room 137, can be supplied with power<br />

from the Building 989 diesel generator. An interruption <strong>of</strong> power will cause the starters for<br />

these pumps to open and the start buttons will have to be pressed to restart the pumps. The<br />

pumps should provide enough circulation to prevent freezing. during power outages during<br />

freezing weather.<br />

2.3.2.4 WAC Chilled Water System<br />

A multiple compressor unit located in Room 130 supplies chilled water to the S-3<br />

system. A cooling water sump and circulating pump, located in Room 130, provide condensing<br />

water and a chilled water pump, located by the unit, circulated chilled water through the chiller<br />

and to the S-3 plenum and to the coil units in the south end <strong>of</strong> the building. Chilled water pump<br />

P-8 circulates water through a three-way valve and the coil in S-3 plenum for cooling. A<br />

pneumatic controller in the S-3 control cabinet modulates the three-way valve to maintain fan<br />

discharge <strong>of</strong> 55°F.<br />

Chilled water is supplied to the fan coil units located in Rooms 101 through 122. Each<br />

unit has a multiple speed fan with a control by the unit. By varying the speed <strong>of</strong> the fan the<br />

desired level <strong>of</strong> cooling for the space is attained. The room thermostats in this area do not<br />

control anything in this system. A chilled water controller in the control cabinet operates the<br />

compressors to maintain a chilled water temperature <strong>of</strong> 45°F. The system is manually operated<br />

and is started as required during the spring, summer and fall months.<br />

2.33 Life Safety/Disaster Warning System<br />

The Building 991 Complex Life SafetyDisaster Warning (LS/DW) System provides<br />

annunciation to building workers for emergency response actions and general building<br />

announcements. The LS/DW system is a multiple-input, Site-wide, public address system. The<br />

LSDW system in the Building 991 Complex is used to make emergency announcements and to<br />

alert personnel <strong>of</strong> hazardous situations, such as airborne contamination, fires, emergency<br />

response activities, or impending natural disasters. The microphone input is located close to the<br />

building entrance in Room 113. Continuously playing music and Site-wide announcements are<br />

generated from the CAS in Building 121. The CAS dispatcher can selectively communicate<br />

with individual buildings or the entire Site via an intercom system.<br />

Revision L<br />

Smlcmhcr 1999<br />

Building 991 Complex FSAR

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!