Figure 8.3 A typical thermostatically controlled food<br />
servery<br />
it is not intended <strong>to</strong> recover the aspects here; however,<br />
failing thermocouples and other heat controlling devices<br />
can also cause fi res. These generally occur due <strong>to</strong> a<br />
fault and a lack of preventive maintenance and testing,<br />
for example using portable electrical appliance testing<br />
known as PAT testing. This PAT testing only checks the<br />
safety from ‘electrocution risk’ and it is possible that a<br />
damaged heat controlling device will not be identifi ed by<br />
such testing.<br />
The failure of the heat controlling device is then<br />
likely <strong>to</strong> allow the overheating of the food or substance<br />
being cooked which may combust and catch fi re. In<br />
instances where oil is being used <strong>to</strong> cook food, chips,<br />
for example, this raising of the oil’s temperature releases<br />
suffi cient vapours <strong>to</strong> cause the oil <strong>to</strong> reach its fl ash and<br />
then fi re point.<br />
Gas cooking systems incorporate both an ignition<br />
source, by way of a pilot light, and a substantial fuel<br />
source, by way of the gas supply used in the cooking<br />
process. A number of fi res are caused each year from<br />
faulty systems where the pilot light fails and gas is released<br />
<strong>to</strong> mix with the air until an explosive concentration is<br />
reached and any alternative ignition sources such as a light<br />
switch are capable of causing an explosion or fi re.<br />
Regardless of the type of cooking device used, if<br />
left unattended an overheated cooking receptacle and/<br />
or food that is allowed <strong>to</strong> burn dry will produce suffi cient<br />
heat for a fi re <strong>to</strong> start.<br />
8.1.3 Naked lights and fl ames<br />
By their nature lighting units emit heat; the amount of heat<br />
will generally depend upon two fac<strong>to</strong>rs, the wattage or<br />
energy consumption and the type of light, such as halogen<br />
lamps, incandescent units or fl uorescent strip lighting.<br />
138<br />
As in the case of all fi res, the lights themselves will<br />
need <strong>to</strong> be positioned close <strong>to</strong> or <strong>to</strong>uching a combustible<br />
material, or in the case of fl ammable mixtures in air,<br />
provide suffi cient heat or an ignition source <strong>to</strong> ignite the<br />
vapours.<br />
Halogen lighting (high heat output) is becoming<br />
more popular within industry and it used <strong>to</strong> light both<br />
internal and external signage. If the signage itself is<br />
combustible and the halogen unit has been installed<br />
incorrectly or poorly maintained the lighting unit may<br />
come in<strong>to</strong> contact with the signage starting a fi re.<br />
Halogen desk lamps are also in evidence in offi ces<br />
and workshops <strong>to</strong> provide additional task lighting. These<br />
units if poorly positioned and left unattended have the<br />
ability <strong>to</strong> start a fi re.<br />
As in the case of all electrical systems lighting<br />
systems have the ability if poorly maintained or incorrectly<br />
installed <strong>to</strong> provide an ignition source for any available<br />
combustible material.<br />
The inappropriate use of lighting units such as in the<br />
case of inspection lamps used in vehicle workshops is<br />
also known <strong>to</strong> be a cause of fi res in the mechanical and<br />
engineering sec<strong>to</strong>rs of industry.<br />
Naked fl ames are a constant source of ignition<br />
within industry. The fl ame generating devices such as<br />
gas <strong>to</strong>rches, welding units and cutting equipment (oxyacetylene)<br />
account for a number of fi res throughout<br />
industry each year. <strong>Fire</strong>s starting from the use of these<br />
pieces of equipment are generally caused by human<br />
error when using them in close proximity <strong>to</strong> other<br />
combustible or fl ammable materials, poorly maintained<br />
equipment or in appropriate use. These issues will be<br />
discussed later in section 8.2.<br />
8.1.4 Heaters and heating systems<br />
<strong>Fire</strong>s caused by heaters and heating systems can be<br />
divided in<strong>to</strong> two key areas; those that are caused by<br />
faulty systems including poor design, inappropriate installation<br />
or lack of planned preventive maintenance; and<br />
those that are caused by inappropriate use or misuse.<br />
Poor design and installation can allow the heat<br />
produced from the system <strong>to</strong> come in<strong>to</strong> direct contact<br />
with combustible materials, perhaps such as wall<br />
linings through which the system’s ducting is routed. As<br />
previously discussed with regard <strong>to</strong> cooking equipment,<br />
a lack of maintenance may allow heat controlling devices<br />
<strong>to</strong> malfunction. In addition if moving or rotating parts are<br />
included in a heating system any bearings may run dry<br />
or seals fail due <strong>to</strong> a lack of maintenance.<br />
Inappropriate positioning of combustible or fl ammable<br />
items in close proximity <strong>to</strong> heaters and parts of<br />
heating systems may prevent air circulation, causing a<br />
heat build-up, or if these materials are in direct contact<br />
or within range of any radiated heat a fi re may start.