Table 9.10 Categorisation of emergency escape lighting<br />

Type<br />

X Units that are self-contained, i.e. they have an integral<br />

rechargeable battery<br />

Y Units that are provided with a central supply<br />

Mode of operation<br />

0 Non-maintained – not illuminated continuously<br />

1 Maintained – illuminated continuously<br />

2 Combined non-maintained – a luminaire containing<br />

two lamps, at least one of which is energised from the<br />

emergency supply not illuminated continuously<br />

3 Combined maintained – a luminaire containing two<br />

lamps, which are maintained from the emergency<br />

supply<br />

4 Compound non-maintained – self-contained unit that<br />

can provide power <strong>to</strong> a satellite unit not illuminated<br />

continuously<br />

5 Compound maintained – self-contained unit that<br />

can provide power <strong>to</strong> a satellite unit illuminated<br />

continuously<br />

6 Satellite – individual unit that is powered from a<br />

compound unit<br />

Facilities<br />

A The unit includes a local test device<br />

B The unit includes a device for remote testing<br />

Duration of operation in minutes<br />

60 Has a duration of 1 hour<br />

120 Has a duration of 2 hours<br />

180 Has a duration of 3 hours<br />

X 0<br />

A<br />

this unit has a local test facility<br />

180<br />

Figure 9.52 An indicative label classifi cation for emergency<br />

escape lighting<br />

Once a system has been installed it is necessary<br />

<strong>to</strong> ensure that its continued operation is effectively<br />

moni<strong>to</strong>red. Those who fi nd themselves responsible for<br />

the means of escape within buildings will need <strong>to</strong> ensure<br />

that the emergency escape lighting system:<br />

➤ Is certifi ed as complying with BS 5266<br />

➤ Is subject <strong>to</strong> routine testing and inspection:<br />

➤ Daily <strong>to</strong> ensure maintained lamps are illuminated<br />

➤ Monthly <strong>to</strong> ensure each unit activates on a failure<br />

of the power supply<br />

<strong>Fire</strong> protection in buildings<br />

Figure 9.53 Maintained emergency exit box<br />

Figure 9.54 Maintained blade emergency light – double<br />

sided<br />

Figure 9.55 Non-maintained satellite emergency light<br />

➤ Six monthly <strong>to</strong> ensure that the unit maintains<br />

emergency operation for at least 1 hour<br />

➤ Three yearly (and after the fi rst three yearly test,<br />

annually) <strong>to</strong> ensure each unit operates for its full<br />

design period.<br />

The moni<strong>to</strong>ring of emergency lighting systems needs <strong>to</strong><br />

form part of the overall management of fi re safety.<br />

9.5.10 Signs and signage<br />

<strong>Fire</strong> safety signs and signing systems form an integral<br />

part of the overall fi re safety strategy of a building and<br />

are fundamental <strong>to</strong> the communication of good fi re<br />

safety management information. Clearly visible and<br />

unambiguous signage is essential for speedy escape,<br />

particularly in buildings where many of the occupants<br />

might be unfamiliar with the building layout.<br />

213