i It should always be ensured that each detector input created in the ETS plug-in is also<br />

linked to a group address and that there is a communication partner in the bus. For detector<br />

monitoring to function, the "Read" flags must be set on the objects to be transmitted by<br />

the bus devices of the detectors.<br />

For each detector to be monitored, it is also important that the group addresses of the detectors<br />

to be transmitted are clear, i.e. are not connected to any other transmitting bus subscriber.<br />

Each messages must have an independent connection to its own detector input on<br />

the signalling system. Only then can it be ensured that only the contacted detector responds<br />

and that detector monitoring is clear.<br />

Order-No. 7574 00 1X<br />

Software "...590101"<br />

Functional description<br />