In case of fault message,<br />
blockage of additional<br />
fault message<br />
windows<br />
Order-No. 7574 00 1X<br />
No presetting This parameter opens a separate dialog,<br />
in which it is possible to specify which of<br />
the other fault messages are blocked<br />
when this signal is activated.<br />
h Fault messages -> [Fault message designation] -> Message window<br />
Open message window Yes<br />
No<br />
Record sender address Yes<br />
No<br />
It is possible to specify here whether a<br />
message window is also displayed on<br />
the panel when a fault occurs. If the<br />
message window is displayed, the signal<br />
can be acknowledged there.<br />
The physical addresses of the devices,<br />
which have activated or deactivated a<br />
fault message, can be recorded in the<br />
message list.<br />
This parameter is only visible on "Open<br />
message window = Yes".<br />
Text, line 2 No presetting The second line of the display text of the<br />
fault message in the message window<br />
can be specified here.<br />
This parameter is only visible on "Open<br />
message window = Yes".<br />
Text, line 3 No presetting The third line of the display text of the<br />
fault message in the message window<br />
can be specified here.<br />
This parameter is only visible on "Open<br />
message window = Yes".<br />
Display external text on<br />
fault message<br />
Yes<br />
No<br />
h Fault messages -> [Fault message designation] -> Acknowledgement<br />
Acknowledgment via<br />
button<br />
Only internal effect<br />
Transmits object value 0<br />
Transmits object value 1<br />
Disabled<br />
Software "...590101"<br />
Parameters<br />
If this parameter is set to "Yes", then an<br />
additional 14 byte object becomes visible,<br />
which can receive a text message.<br />
This text is then also displayed in the<br />
message window. To receive this external<br />
text, the display of the message<br />
window is delayed internally.<br />
This parameter is only visible on "Open<br />
message window = Yes".<br />
This parameter defines whether an acknowledgement<br />
in the message window<br />
has a purely internal effect or whether<br />
the acknowledgement is also transmitted<br />
to the bus via an acknowledgement<br />
object. The latter is advisable if, for example,<br />
a fault is signalled on multiple<br />
bus subscribers and acknowledgement<br />