4.2.4.6 Timer switch function<br />

Timer switch<br />

The panel possesses an integrated weekly timer switch with up to 16 channels, which are split<br />

into two timer switch pages of eight channels. The timer switch pages are predefined as system<br />

pages can be jumped to by pressing a function button to open a page.<br />

Order-No. 7574 00 1X<br />

picture 23: Timer switch page<br />

Eight switching times can be assigned to each channel. The weekdays can be freely selected<br />

for each switching time. The switching times can be programmed as a specification in the ETS<br />

plug-in or directly on the panel at any time after commissioning using the timer switch pages. In<br />

addition, a random function and an astro function for time-dependent lighting or shading control<br />

can be activated on each timer switch channel.<br />

The timer switch is controlled by the internal real time clock of the panel. If the<br />

230 V power supply fails, the internal clock runs on for approx. 24 hours. When the power supply<br />

returns, the timer switch checks to see if switching times were programmed for this period.<br />

In this case, the last programmed command is carried out for the affected channels.<br />

When the internal clock is resynchronised, a distinction is to be made between two cases...<br />

- The clock is moved back to a time before an already executed switching time. In this case,<br />

the programmed command is executed again when the switching time occurs.<br />

- The clock is moved forward to a time after an as yet unexecuted switching time. In this<br />

case, the last programmed command of the channel is carried out.<br />

4.2.4.6.1 Creating timer switch channels<br />

Software "...590101"<br />

Functional description<br />

When the timer switch channels are created, a display element is generated on the appropriate<br />

timer switch page. A timer switch channel is added by clicking the right mousebutton in the<br />

parameter node "Timer switch -> Timer switch page...".<br />

As with the display elements on the planned used pages, each timer switch channel also possesses<br />

a designation, which only appears in the tree structure of the ETS plug-in and a text<br />

which is displayed on the screen. This text can be positioned horizontally in the display element.<br />

One of four functions can be assigned to each timer switch channel using the "Function" parameter...<br />

- Switching<br />

- Value<br />

- Light scene<br />

- Operating mode switch<br />